Installation Instructions
Fuel Field Kit Installation Instructions
Fuel Field Kit Installation Sheet for Australian HSB 3
2. See Figure 4. Mount DIN rail (A) to drilled holes in
engine divider panel with two M4-0.7 X 10 (8-32 x
0.
5 in) fasteners and nuts.
005670
B
A
B
C
Figure 4. Mount DIN Rails and Relays
NOTE: B
oth control relays (B) mount to DIN rail through
eyelets provided on the relays.
3. Clip
timer relay (C) onto DIN rail between the two
control relays.
Timer Relay Settings
See Figure 5. Timer relay includes an adjustable timing
dial (1), a fine time dial (2) to be set full c
lockwise, and a
function dial (3) to be set at “D.”
006094
1 sec-
10 day
1
10
ON
OFF
1
1
10
1
10
10
m
S
h
d
B
A
C
D
E
F
G
H
I
J
3
1
2
Figure 5. Timer Relay Settings
Connecting the Wires
Proceed as follows to connect kit wires:
1. Wire
control relays and timer relay per Wiring Dia-
gram—AU Fuel Field Install Kit and Wire Gauge
and Length Chart.
2. Con
nect kit wire Q to unit harness wire #86 by
inserting and crimping the 6 mm stripped end of kit
wire Q into factory connected bullet connector
hanging near battery charger plug.
3. Disco
nnect unit harness #14 wire (red) at the fuel
solenoid and connect it to kit wire D.
4. Con
nect kit wire C to exposed fuel solenoid termi-
nal.
5. Con
nect kit wire P to unit harness wire #56 by
inserting and crimping the 6 mm stripped end of kit
wire P into factory connected blade connector
hanging near battery charger plug.
6. Insta
ll fuel pressure sensor(s) in line with fuel sup-
ply. Configure to correct setting for desired fuel
ty
pe using fuel pressure switch manual.
7. Rou
te kit wires G, H, and S from inside unit out to
fuel pressure sensor switch(es).
8. V
erify all other wire connections per wire diagram.
Complete Installation
(000167a)
Equipment damage. Do not make battery
connections in reverse. Doing so will result
in equipment damage.
CAUTION
Proceed as follows to complete installation:
1. Clea
n drilling and other debris from enclosure.
2. Con
nect positive battery cable first, then negative
battery cable.
3. Insta
ll intake side panel.
4. Insta
ll 7.5 amp fuse in control panel.
5. Set gen
erator set MLCB (generator set disconnect)
to ON (CLOSED).
6. Set mains
MLCB to ON (CLOSED).
NOTE: V
erify functionality of fuel kit prior to completing
installation and leaving unit in AUTO mode.