Installation Instructions

011479
Fuel Field Kit Installation Instructions
Fuel Field Kit Installation Sheet for Australian HSB 2
Figure 1. Completed Gas Train
Installation Instructions
(000191)
DANGER
Automatic start-up. Disconnect utility power and
render unit inoperable before working on unit.
Failure to do so will result in death or serious injury.
Throughout this procedure, see Wire Gauge and Length
Chart, wiring diagram, schematic diagram, and splice
diagram at the end of this section.
Preparing Generator
(000238)
Explosion. Batteries emit explosive gases.
Always disconnect negative battery cable
first to avoid spark. Failure to do so could
result in death or serious injury.
WARNING
NOTE: This fuel field install kit requires components to
be installed in the fuel supply piping to generator set. Ver-
ify fuel is correctly shut off prior to installing fuel pressure
switch(es).
Proceed as follows to prepare generator set for fuel field
kit ins
tallation:
1. Set m
ains main line circuit breaker (MLCB) to OFF
(OPEN).
2. L
ift enclosure lid and set generator set MLCB (gen-
erator set disconnect) to OFF (OPEN).
3. Pr
ess OFF button on controller.
4. Rem
ove 7.5 amp fuse from control panel.
5. Remove intake side panel.
6. Disco
nnect battery cables, removing negative bat-
tery cable first.
Installing DIN Rail and Relays
Proceed as follows to install DIN rail and relays:
1. See Figure 2 or Figure 3. Drill two 5 mm (0.20 in)
holes in upper right corner of engine divider panel
un
der controller.
005669
2X Ø 5 mm
(0.20 in.)
170 mm
(6.69 in)
100 mm
(3.94 in)
36 mm
(1.42 in)
NOTE: Avoid damaging harness wires and decals while
drilling.
Figure 2. Hole Locations—8 kV
A Engine Divider
Panel
006808
2X Ø 5 mm
(0.20 in.)
125 mm
(4.92 in)
36 mm
(1.42 in)
100 mm
(3.94 in)
Figure 3. Hole Locations—10, 13, & 20 kVA Engine
Divider Panel