Product Manual

Connecting Lead Wires
2016–Present Units
1. See Figure 12. Pass lead wires through the
customer connection panel grommet (A).
002769
A
Figure 12. Lead Wires to Customer Connection
2. See Figure 13. Connect heater lead wires to T1
terminal (B) and Neutral stud (C) as shown.
005565a
B
C
Figure 13. Input Sense Terminal Block
NOTE: W
ire with ring terminal connects to Neutral bar
stud.
2013–2015 Units
See Figure 14. Connect heater lead wires to T1 terminal
(D) and Neutral stud (E) as shown.
005566
D
E
Figure 14. Input Sense Terminal Block
NOTE: Wir
e with ring terminal connects to Neutral bar
stud.
Completing Installation
Engine damage. Verify proper type and
quantity of oil prior to starting engine.
Failure to do so could result in
engine damage.
ISO000135
Proceed as follows to complete installation:
1. V
erify all wire routings are clear of pinch points and
other damage. Use tie wraps where necessary.
2. I
nstall customer connection panel cover.
3. Insta
ll controller fascia (2013–2015 units) or intake
side panel (2016 and newer units) and front panel.
4. Return utility
power supply to transfer switch:
In service rated transfer switches, turn main
br
eaker ON.
In non-service-rated switches, turn power feeder
breaker ON.
NOTE: If
removed, install T1, T2, N1, and N2 fuses in
the transfer switch.
5. Insta
ll 7.5A fuse in control panel.
6. Complete Install Wiza
rd programming.
7. Pre
ss AUTO mode button on control panel.
8. Set
MLCB (generator disconnect) to ON
(CLOSED).
9. Close and lock lid.
Part No. 10000022351 Rev B 05/16/19
©2019 Generac Power Systems, Inc.
All rights reserved.
Specifications are subject to change without notice.
No reproduction allowed in any form without prior written consent from
Generac Power Systems, Inc.
Generac Power Systems, Inc.
S45 W29290 Hwy. 59
Waukesha, WI 53189
1-888-GENERAC (1-888-436-3722)
www.generac.com