Install Manual

Location and Compliance
10 Installation Manual for Generac PWRcell Inverter
Voltage and Frequency Trip Thresholds
This unit or system is provided with fixed trip limits and
shall not be aggregated above 30 kW on a single point of
common connection.
All Generac PWRcell Inverters are shipped from the fac-
tory in compliance with all UL1741 requirements, includ-
ing IEEE1547. If your installation requires compliance to
a dif
ferent standard, such as UL1741SA, contact the
nearest Independent Authorized Service Dealer (IASD)
or Generac Customer Service at 1-888-436-3722 (1-888-
GENERAC), or visit www.generac.com for assistance.
Voltage Trip Thresholds
See Table 3-2 for the default fixed voltage trip setpoints.
All over voltage and under voltage trip conditions result in
a 300-second restart delay time after the trip threshold
has been exceeded for the listed number of cycles.
Frequency Trip Thresholds
See Table 3-2 for the default fixed frequency trip set-
points. All over frequency and under frequency trip condi-
tions result in a 300-second restart delay time after the
trip threshold has been exceeded for the listed number of
cycles.
Table 3-2. Voltage Trip and Frequency Thresholds
Voltage Trip Thresholds Frequency Trip Thresholds
Threshold
Threshold
(% of nominal)
No. of Cycles Threshold
Hz Over/
Under Nominal
No. of Cycles
OV1 110 120 OF1 0.5 120
OV2 120 10 OF2 2 6
OV3 130 1 OF3 1.3 0
OV4 999* 1 OF4 0** 1
UV1 88 120 UF1 0.5 120
UV2 50 10 UF2 2 10
UV3 0 1 UF3 0** 1
UV4 0 1 UF4 0** 1
*Value of 999 indicates a disabled threshold for voltage trips
**Value of zero indicates a disabled threshold for frequency trips