Control Panel Startup / Testing
36 Installation Guidelines for 60 Hz Air-Cooled Generators
Interconnect System Self Test Feature
This controller goes through a system self test at startup,
which checks for utility voltage on DC circuits. This test
prevents  damage  if  installer  incorrectly  connected  AC
utility power sense wires into the DC terminal block. The
controller will display a warning message and lock out the
generator if utility voltage is detected at the DC terminal
block, preventing damage to the controller. Power to con-
troller must be removed to clear this warning.
Utility voltage must be turned on and present at the N1
and  N2  terminals  inside  the  generator  control  panel  for
this test to be performed and pass.
NOTE:  All  appropriate  panels  must  be  in  place  during
any operation of generator. This includes operation by a
servicing  technician,  while  conducting  troubleshooting
procedures.
Before starting, complete the following:
1. Verify generator is OFF.
2. Set  generator  MLCB  (generator  disconnect)  to
OFF (OPEN).
3. Turn OFF all breakers to be supplied by generator.
4. Verify  auxiliary  shutdown  switch(es)  are  CLOSED
(I).
5. Check engine crankcase oil level and, if necessary,
fill to oil dipstick FULL mark with recommended oil.
Do not overfill.
6. Inspect fuel supply. Gaseous fuel lines must have
been  correctly  purged  and  leak  tested  in  accor-
dance with applicable fuel-gas codes. All fuel shut-
off valves in the fuel supply lines must be open.
During initial startup only, generator may exceed normal
number  of  start  attempts  and  experience  an  “OVER-
CRANK” fault. This is due to accumulated air in the fuel
system during installation. Reset control board by press-
ing OFF mode button and ENTER button, and restart up
to two more times if necessary. If unit fails to start, con-
tact an IASD for assistance.