Operating Guide
Operation
18 Owner’s Manual for 60 Hz Air-Cooled Generators
Operating Modes Interface Menu Displays
LCD Panel
Mode Description
MANUAL
• Will not transfer to standby if utility is present.
• Transfers to standby if utility drops below 65%
of  nominal  for  five  consecutive  seconds
(dealer programmable) after warm-up.
• Transfers back when utility returns for 15 con-
secutive  seconds  (dealer  programmable).
Engine  continues  to  run  until  removed  from
MANUAL.
AUTO
• Starts and runs if utility drops for five consecu-
tive seconds (dealer programmable).
• Starts an engine warm-up timer (duration var-
ies when Cold Smart Start is enabled).
–Will  not  transfer  if  utility  subsequently
returns.
–Transfers to standby if utility is not present.
• Transfers  to  utility  once utility  returns  (above
80%  of  nominal)  for  15  consecutive  seconds
(dealer programmable).
• Will not transfer to utility unless utility returns.
Unit will shut down if OFF button is pressed or
a shutdown alarm is present.
• Unit will shut down after one minute cool-down
time when utility power returns.
EXERCISE
• Will  not  exercise  if  unit  is  already  running  in
either AUTO or MANUAL.
• During exercise, controller will only transfer if
utility  drops  during  exercise  for  five  seconds
(dealer  programmable),  and  will  switch  to
AUTO.
Feature  Description
HOME 
page
Default  page  displayed  if  no  buttons  are
pressed for 60 seconds. Normally shows cur-
rent  status  message,  and  current  date  and
time. Highest  priority  active  alarm/warning  is
automatically posted on this page, as well as
flashing the backlight when such a condition
is  detected.  In  the  case  of  multiple  alarms/
warnings,  only  first  message  is  displayed.
Press OFF button and then ENTER button to
clear an alarm or warning.
When “Hours of Protection” is displayed, this
represents  total  time  generator  has  been
monitoring utility supply and ready to provide
backup power if needed. 
Display 
Backlight
Normally  off. The  backlight will automatically
illuminate  and  remain  on  for  30  seconds  if
operator presses any button. 
MAIN 
MENU 
page
Allows operator to navigate to all other pages
or  sub-menus  by  using  arrow  keys  and
ENTER button. Page can be accessed at any
time  with  several  presses  of  the  dedicated
ESCAPE button. Each press of the ESCAPE
button takes operator to previous menu until
MAIN  MENU  displays.  This  page  contains
information  for  History;  Status;  Edit;  and
Debug.