Operating Guide
Operation
Owner’s Manual for 60 Hz Air-Cooled Generators 17
Auxiliary Shutdown Switch
All  generators  are  equipped  with  an  external  means  of
shutting down the generator which complies with the lat-
est NEC code requirement. Primary generator shutdown
sequence  is  described  in  Shutting  Generator  Down
While Under Load or During a Utility Outage. 
See  Figure  3-6.  An  auxiliary  shutdown  switch  (A)  is
located on the exterior of the generator back panel. This
auxiliary shutdown switch shuts down generator and dis-
ables restarts. 
Figure 3-6. External Auxiliary Shutdown Switch      
(all models)
NOTE:  Whenever  possible,  perform  primary  shutdown
procedure before disabling generator with auxiliary shut-
down switch.
See Figure 3-7. 14–24 kW generators also have an aux-
iliary shutdown switch (A) located inside generator.
Figure 3-7. Internal Auxiliary Shutdown Switch 
(14–24kW)
NOTE:  Generator will not start if either switch is  OPEN
(O).  Controller  displays  an  “Auxiliary  Shutdown”  alarm,
and red LED “Alarm” light illuminates. To clear this condi-
tion, set switch or switches to CLOSED  (I). Clear  alarm
by pressing OFF button, and then ENTER. The generator
can then be placed in AUTO or MANUAL.
Control Panel Interface
See Figure 3-8. The control panel interface (A) is located
under  the  enclosure  lid.  Verify  both  left  and  right  side
locks are  unlocked before attempting to  lift  lid of  enclo-
sure. Open lid as directed in Opening the Lid.
Figure 3-8. Generator Control Panel
The 7.5A fuse is located beneath rubber cover (B) to the
right of the control panel.
Verify both left and right side locks are securely out of the
way before closing unit. 
All appropriate panels must be in place during any opera-
tion of the generator. This includes operation by a servic-
ing  technician  while  conducting  troubleshooting  pro-
cedures.
Using the AUTO/OFF/MANUAL 
Buttons
NOTE:  Damage  caused  by  mis-wiring  of  interconnect
wires is not warrantable.
Equipment Damage. The auxiliary shutdown switch 
is not to be used to power down the unit under 
normal operating circumstances. Doing so will 
result in equipment damage.
(000399)
CAUTION
005492
A
005491
A
Button  Description of Operation
AUTO
Activates  fully  automatic  system  operation.
Allows  unit  to  automatically  start  and  exercise
generator according to exercise timer (see Set-
ting the Exercise Timer). 
Green  LED  flashes  when  automatic  transfer
switch  converts  to  generator  power  during  a
utility power outage.
OFF
Shuts  down  engine  and  prevents  automatic
operation of unit.
MANUAL
Cranks and starts generator. Transfer to stand-
by power will not occur unless there is a utility
failure.
Blue  LED  flashes  when  automatic  transfer
switch  converts  to  generator  power  during  a
utility power outage.
001798
A
B