Installation Guide
Table Of Contents
- Installation Guidelines 60 Hz Air-Cooled Generators
- Table of Contents
 - Section 1: Safety Rules & General Information
 - Section 2: Unpacking and Inspection
 - Section 3: Site Selection and Preparation
 - Section 4: Generator Placement
 - Section 5: Fuel Conversion / Gas Connections
 - Section 6: Electrical Connections
 - Section 7: Control Panel Startup / Testing
 - Section 8: Troubleshooting
 - Section 9: Quick Reference Guide
 - Section 10: Accessories
 - Section 11: Diagrams
 
 

Control Panel Startup / Testing
Installation Guidelines for 60 Hz Air-Cooled Generators 33
Section 7: Control Panel Startup / Testing
Control Panel Interface
The  control  panel  interface  is  located  under  the  enclo-
sure lid. Verify both left and right side locks are unlocked
before  attempting  to  lift  enclosure  lid.  Open  lid  as
directed in Opening the Lid.
Using the AUTO/OFF/MANUAL Buttons
Figure 7-1. Generator Control Panel
Generator Setup
The controller illuminates when battery power is applied
to  generator  during  the  installation  process.  Generator
must  be  activated  before  it  will  automatically  run  in  the
event of a power outage.
Activation
To  activate the  generator,  go  to  www.activategen.com
and follow the instructions.
Activation is  a  simple,  one-time process. The  generator
will  not  prompt  to  activate  again  once  the  unit  is  acti-
vated,  even  if  the  generator  battery,  fuse,  and  battery
charge circuit (T1) are disconnected. 
NOTE:  The generator  must  be  connected  to  the  home
Wi-Fi  network  for  automatic  authentication  to  be
completed  successfully.  See  Wi-Fi  manual  for  more
information.
NOTE:  If  home  Wi-Fi  network  is  not  available,  follow
instructions on www.activategen.com.
Proceed as follows after activating generator on-line:
1. The  display  interface  will  launch  Install  Wizard
upon first power-up of the generator.
2. Follow  on-screen  instructions  on  the  generator
along with Quick Start Guide supplied with the unit
to connect generator to home Wi-Fi network.
3. Wait for on-line authentication of generator activa-
tion through connected home Wi-Fi network.
4. Follow  on-screen  instructions  to  complete  the
Install Wizard.
NOTE:  See  Figure  7-2.  If  generator  screen  shows
message shown below, press ESC and  then ENTER to
reset to Install Wizard.
Figure 7-2. Not Activated Screen
NOTE:  Generator  can  only  be  placed  in AUTO  mode
after completing activation process.
IMPORTANT  NOTE: Fuel selector knob must be set
to the correct fuel for generator to function correctly.
Button  Description of Operation
AUTO Activates fully automatic system operation. Auto-
matic operation allows unit to automatically start
and  exercise  generator  according  to  exercise
timer  settings  (see  Setting  The  Exercise
Timer).
OFF Shuts down engine and also prevents automatic
operation and exercise of unit.
MANUAL Cranks and starts generator. Transfer to standby
power will not occur unless there is a utility fail-
ure.
000425
NOT ACTIVATED!
XXX (H)
009102










