Replacement Part List

4 of 6
®
Generator
Model G007038-1
G007039-1
(20 kW)
G007042-2
G007043-2
(22 kW)
G007038-3
G007039-3
(20 kW)
G007042-3
G007043-3
(22 kW)
G007209-0
G007210-1
(24 kW)
Rated maximum continuous power capacity (LP) 20,000 Watts* 22,000 Watts* 20,000 Watts* 22,000 Watts* 24,000 Watts*
Rated maximum continuous power capacity (NG) 18,000 Watts* 19,500 Watts* 18,000 Watts* 19,500 Watts* 21,000 Watts*
Rated voltage 240
Rated maximum continuous load current – 240 volts (LP/NG) 83.3 / 75.0 91.7 / 81.3 83.3 / 75.0 91.7 / 81.3 100 / 87.5
Total Harmonic Distortion Less than 5%
Main line circuit breaker 90 amp 100 amp 90 amp 100 amp 100 amp
Phase 1
Number of rotor poles 2
Rated AC frequency 60 Hz
Power factor 1.0
Battery requirement (not included) 12 Volts, Group 26R 540 CCA minimum or Group 35AGM 650 CCA minimum
Unit weight (lb / kg) 448 / 203 466 / 211 436 / 198 445 / 202 455 / 206
Dimensions (L x W x H) in / cm 48 x 25 x 29 / 121.9 x 63.5 x 73.7
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load** 67 67 67 67 67
Sound output in dB(A) at 23 ft (7 m) with generator in Quiet-Test™ low-speed exercise mode** 55 57 55 57 57
Exercise duration 5 min
Engine
Engine type GENERAC G-Force 1000 Series
Number of cylinders 2
Displacement 999 cc
Cylinder block Aluminum w/ cast iron sleeve
Valve arrangement Overhead valve
Ignition system Solid-state w/ magneto
Governor system Electronic
Compression ratio 9.5:1
Starter 12 VDC
Oil capacity including filter Approx. 1.9 qt / 1.8 L
Operating rpm 3,600
Fuel consumption
Natural gas ft³/hr (m³/hr)
1/2 Load
Full Load
Liquid propane ft
3
/hr (gal/hr) [L/hr]
1/2 Load
Full Load
204 (5.78)
301 (8.52)
87 (2.37) [8.99]
130 (3.56) [13.48]
228 (6.46)
327 (9.26)
92 (2.53) [9.57]
142 (3.90) [14.77]
164 (4.64)
287 (8.13)
86 (2.36) [8.95]
136 (3.74) [14.15]
203 (5.75)
306 (8.66)
92 (2.53) [9.57]
142 (3.90) [14.77]
Note: Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet at all load ranges - 3.5–7 in water column (0.87–1.74 kPa) for NG, 10–12 in water column (2.49–2.99 kPa) for LP
gas. For BTU content, multiply ft
3
/hr x 2500 (LP) or ft
3
/hr x 1000 (NG). For Megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG).
Controls
Two-line plain text multilingual LCD Simple user interface for ease of operation.
Mode buttons: AUTO Automatic start on utility failure. Weekly, Bi-weekly, or Monthly selectable exerciser.
MANUAL Start with starter control, unit stays on. If utility fails, transfer to load takes place.
OFF Stops unit. Power is removed. Control and charger still operate.
Ready to Run/Maintenance messages Standard
Engine run hours indication Standard
Programmable start delay between 2–1500 seconds Standard (programmable by dealer only)
Utility Voltage Loss/Return to Utility adjustable (brownout setting) From 140-171 V / 190-216 V
Future Set Capable Exerciser/Exercise Set Error warning Standard
Run/Alarm/Maintenance logs 50 events each
Engine start sequence Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration).
Starter lock-out Starter cannot re-engage until 5 sec after engine has stopped.
Smart Battery Charger Standard
Charger Fault/Missing AC warning Standard
Low Battery/Battery Problem Protection and Battery Condition indication Standard
Automatic Voltage Regulation with Over and Under Voltage Protection Standard
Under-Frequency/Overload/Stepper Overcurrent Protection Standard
Safety Fused/Fuse Problem Protection Standard
Automatic Low Oil Pressure/High Oil Temperature Shutdown Standard
Overcrank/Overspeed (@ 72 Hz)/rpm Sense Loss Shutdown Standard
High Engine Temperature Shutdown Standard
Internal Fault/Incorrect Wiring protection Standard
Common external fault capability Standard
Field upgradable firmware Standard
**Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters. Rating definitions - Standby: Applicable for supplying
emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). * Maximum kilovolt amps and current are
subject to and limited by such factors as fuel BTU/megajoule content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases approximately 3.5% for each 1,000 ft (304.8 m) above sea
level; and also will decrease approximately 1% for each 10 °F (6 °C) above 60 °F (16 °C).
20/22/24 kW
20/22/24 kW Specifications