Operating Guide
Operation
Owner’s Manual for 60 Hz Air-Cooled Generators 23
Load Transfer
The transfer of load when generator is running is depen-
dent upon operating mode.
Shutting Generator Down While 
Under Load or During a Utility Outage
IMPORTANT NOTE: To avoid equipment damage, 
follow  these  steps,  in  order,  during  utility  outages. 
Shutdowns may be required during utility outages to 
perform routine maintenance or to conserve fuel.
To turn generator OFF:
1. Set main utility disconnect to OFF (OPEN).
2. Set  generator  MLCB  (generator  disconnect)  to 
OFF (OPEN).
3. Allow  generator  to  run  for  cool-down  for  approxi-
mately one minute.
4. Set generator to OFF at the controller.
5. Remove 7.5A fuse from controller.
To turn generator back ON:
1. Install 7.5A fuse in controller.
2. Verify  generator  MLCB  (generator  disconnect)  is 
OFF (OPEN).
3. Set generator to AUTO mode at the controller.
4. Generator will start and run. Allow generator to run 
and warm up for a few minutes.
5. Set  MLCB  (generator  disconnect)  to  ON 
(CLOSED).
6. Set main utility disconnect to ON (CLOSED).
The system now operates in automatic mode. 
Automatic start-up. Disconnect utility power and 
render unit inoperable before working on unit. 
Failure to do so will result in death or serious injury.
(000191)
DANGER










