Operating Guide
Maintenance
Owner’s Manual for 60 Hz Air-Cooled Generators 31
Always  recycle  batteries  in  accordance  with  local  laws 
and regulations. Contact your local solid waste collection 
site or recycling facility to obtain  information on local 
recycling processes.  For  more  information on  battery 
recycling,  visit  the  Battery  Council  International  website 
at: http://batterycouncil.org
Strictly observe  the  following precautions when  working 
on batteries:
• Remove 7.5A fuse from generator control panel.
• Disconnect battery charger as directed in Battery 
Maintenance.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not place tools or metallic objects on top of bat-
tery.
• Disconnect charging source prior to connecting or 
disconnecting battery terminals.
• Wear full eye protection and protective clothing.
• If electrolyte contacts skin, wash it off immediately 
with water.
• If  electrolyte  contacts  eyes,  flush  thoroughly  with 
water immediately and seek medical attention.
• Wash down spilled electrolyte with an acid neutral-
izing agent. A common practice is to use a solution 
o
f 1 lb (454 g) bicarbonate of soda to 1 gal (3.8 L) 
of water. Add bicarbonate of soda solution until evi-
dence  of  reaction  (foaming)  has  ceased.  Flush 
re
sulting liquid with water and dry area completely.
• DO NOT smoke near battery.
• DO NOT cause flame or spark in battery area.
• Discharge  static  electricity from the body  before 
touching battery by first touching a grounded metal 
surface.
Battery  should  be  regularly  inspected  per  Service 
Schedule. Contact an IASD for assist
ance if necessary.
Inspecting the Battery
Proceed as follows to inspect battery:
1. Pre
ss OFF button to shut down generator, then lift 
lid and remove front panel.
2. Remov
e 7.5A fuse from control panel.
3. Remo
ve intake side panel. (See Intake Side Panel 
Removal.)
4. See  Figure 4-9. Inspect battery  posts  and  cables 
for  tightness  and  corrosion.  Tighten  and  clean  as 
ne
cessary.
–
+
001832
Figure 4-9. Battery Cables
5. Unsealed  batteries  only: 
Completely  disconnect 
battery. Check battery fluid level and, if necessary, 
fill with distilled water only. DO NOT use tap water. 
Have an IASD or a qualified service technician ver-
ify state of charge an
d condition.
6. Con
nect  battery  cables,  install  intake  side  panel, 
and install 7.5 A fuse when inspection is complete.
7. Pr
ess AUTO button on controller.
8. Insta
ll front panel and close generator lid.
(000138a)
WARNING
Risk of burns. Batteries contain sulfuric acid and 
can cause severe chemical burns. Wear protective 
gear when working with batteries. Failure to do 
so could result in death or serious injury.
WARNING
(000228)
Environmental Hazard. Always recycle batteries at an 
official recycling center in accordance with all local 
laws and regulations. Failure to do so could result in 
environmental damage, death, or serious injury.