Operating Guide
Operation
22 Owner’s Manual for 60 Hz Air-Cooled Generators
7. Set  MLCB  (generator  disconnect)  to  ON 
(CLOSED).  Standby  power  source  now  powers 
loads.
Transfer to Utility Power Source
Shut  down  generator  and  transfer  to  utility  source  after 
utility  power  has  been  restored.  Proceed  as  follows  to 
manually transfer to utility power and shut down genera-
tor:
1. Set MLCB (g
enerator disconnect) to OFF (OPEN).
2. Run 
engine  for  one  minute  at  no-load  to  stabilize 
internal temperature.
3. Press
 OFF button  on control panel. Engine will 
shut down.
4. V
erify  utility  power  supply  to  transfer  switch  is 
turned off.
5. Set 
main contacts to UTILITY (loads connected to 
utility power source) using manual transfer handle 
(A in Figure 3-11) inside transfer switch.
6. T
urn on utility power supply to transfer switch using 
means provided.
7. Pr
ess AUTO button on control panel. 
8. Retur
n  MLCB  (generator  disconnect)  to  ON 
(CLOSED).
9. Close and lock lid.
Automatic Transfer Operation
Proceed as follows to select automatic operation:
1. V
erify transfer switch main contacts are set to 
UTILITY (loads connected to utility power source).
2. V
erify normal utility power source  voltage is avail-
able to loads connected to transfer switch.
3. Pr
ess AUTO button on control panel.
4. Set 
MLCB  (generator  disconnect)  to  ON 
(CLOSED).
Generator will start automatically
 when utility source volt-
age drops below a preset level. Loads are transferred to 
stand
by power source after unit starts.
Automatic Sequence of Operation
Utility Failure
If generator is set to AUTO when utility fails (below 65% 
of  nominal),  a  five  second  (dealer  programmable)  line 
interrupt  delay  time  is  started.  The  engine  cranks  and 
starts  if  utility  power  is  still  unavailable  when  timer 
expires. An  engine  warm-up  timer  will  be  initiated  once 
engine  is  started.  Timer  duration  varies  depending  on 
whether or not Cold Smart Start is enabled. The control-
ler  will  transfer load  to  generator 
when  warm-up  time 
expires. If utility power is restored (above 80% nominal) 
at any time from initiation of engine start until generator is 
ready to accept load (warm-up time has not elapsed), the 
controller  completes  start  cycle  and  runs  generator 
through  its  normal  cool  down  cycle.  However,  load  will 
remain on utility source.
Cranking
The system will control the cyclic cranking as follows:
• 10  kW  Unit:  five  cranking  cycles  as  follows:  15 
seconds cranking, seven seconds resting, followed 
by four additional cycles  of  seven  seconds crank-
ing followed by seven seconds resting.
• 13–22 kW  Units:  five  cranking  cycles  as  follows: 
16  seconds  cranking,  seven  seconds  resting,  16 
seconds cranking, seven seconds resting, followed 
by three additional cycles of seven seconds crank-
ing followed by seven seconds resting.
NOTE: An 
alarm will be triggered if generator does not 
start after these five attempts.
Cold Smart Start
Cold Smart Start is factory-enabled, but can be disabled 
in  the  EDIT  menu.  Generator  will  monitor  ambient  tem-
perature when Cold Smart Start is enabled. The warm-up 
delay w
ill be adjusted based on prevailing conditions. 
See  Table 3-2. If ambient temperature is below a fixed 
temperature  (based  on  model)  upon  startup  in  AUTO, 
generator 
will  warm  up  for  30  seconds.  This  allows 
engine to warm before a load is  applied. The generator 
will startup with normal warm-up delay of five seconds if 
ambient  temperature  is  at  or  above  the  fixed  tempera-
ture.
Table 3-2. Cold Smart Start Set Points
Generator Size 10 kW–20 kW 22 kW
Fixed Temperature 50 °F (10 °C) 20 °F (-7 °C)
A  check  for  correct  output  voltage  buildup  will  be  per-
formed when generator engine is started.
Cleaning Cycle 
If some condition impedes normal voltage creation, such 
as frost crystals or dust/dirt preventing a good electrical 
connection, start sequence will be interrupted so a clean-
ing  cycle  of  the  internal  e
lectrical  connections  can  be 
attempted.
Cleaning  cycle is  an  extended  warm  up  period  which 
lasts 
for several minutes while normal generator voltage 
output is determined to be low. During this cycle, genera-
tor  controller  will  display  “W
arming  Up”  on  the  display 
screen.
The  generator  controller 
display  will  show  “Under  Volt-
age” if cleaning cycle fails to clear the obstruction. After 
sever
al minutes, alarm message can be cleared, and the 
generator restarted.
If the problem persists, make no further attempts to start. 
Co
ntact an IASD.










