Cut Sheet
Table Of Contents
Model No. 0066130 Home Standby Remote Start Kit
Instruction Sheet 7
7. Use the up/down arrow keys to scroll through the parameters until 2 WIRE START SELECT is displayed. Press ENTER to select this param-
eter as the one to be edited.
8. Use the up/down arrow keys to change the display to read YES.
9. Press ENTER to store the data. Remote start is now enabled.
10. Place the generator switch in the AUTO mode (green light on the control panel is ON).
11. After completing installation, verify that the two wire start is functioning properly.
4. PowerPact™ Controller (2014 and later)
1. Open the controller/circuit breaker cover to access the generator’s controller panel.
2. Place the generator in the OFF mode by pressing the OFF button.
3. Remove and retain the 7.5 Amp ATO
® fuse.
4. Remove the four fasteners from the top cover of the enclosure. Lift the top cover from the generator.
5. Remove the two fasteners and remove the battery access panel inside the enclosure.
6. Disconnect the black (-) negative lead from the battery.
4.1 - Wiring
Two wires need to be added to the wire harness. One wire between the ground terminal block and start switch.
See the back side of the controller for Steps 1-12.
1. Unplug the 20 pin wire harness connector (J5) from the controller panel by carefully releasing the latch on the side of the connector. See Fig-
ure 6.
2. Insert the crimp end of wire #0 (0J0973E) into location 3 on the wire harness connector (J5).
3. Connect the other end, with the ring terminal, to the ground screw on the rear of the customer connection box.
4. Insert the crimp end of wire #183 (0J0973D), into location 7 on the wire harness connector (J5).
5. Connect the other end of wire #183 to the start switch.
6. Plug the harness connector back into (J5) on the backside of the controller.
7. Connect the ring terminal end of wire #178 (0J0973C) to the ground screw on the rear of the connection box.
8. Connect the other end of wire # 178 to the start switch.
9. Reconnect the black (-) negative lead to the battery.
10. Install the battery access panel and tighten the two fasteners securely.
11. Install the enclosure’s top cover. Tighten all four fasteners securely.
12. Install the 7.5 Amp ATO
® fuse.
13. Press the AUTO button to place the generator in the AUTO mode.
14. After completing installation, verify that the two wire start is functioning properly.
NOTE: The exercise function will need to be reset every time the 12 volt battery and T1 power to the generator are disconnected and
then reconnected, and/or when the fuse is removed and T1 power is removed from the generator.