Spec Sheet

3 of 5
®
Generator
Model G006998-1
Rated maximum continuous power capacity (LP) 7,500 Watts*
Rated maximum continuous power capacity (NG) 6,000 Watts*
Rated voltage 240
Rated maximum continuous load current – 240 volts (LP / NG) 31.25 / 25
Main line circuit breaker 35 amp
Phase 1
Number of rotor poles 2
Rated AC frequency 60Hz
Power Factor 1.0
Battery requirement (not included) Group U1, 12 volts and 300 CCA minimum
Unit weight (lb / kg) 280 / 127.3
Dimensions (L x W x H) in / cm 36 x 27 x 25 / 91.5 x 67.6 x 64.0
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load**
69
Engine
Engine type GENERAC OHV
Number of cylinders 1
Displacement 420 cc
Cylinder block Aluminum w/ cast iron sleeve
Valve arrangement Overhead valve
Ignition system Solid-state w/ magneto
Governor system Mechanical
Starter 12 VDC
Oil capacity including filter Approx. 1.2 qt/1.1 L
Operating rpm 3,600
Fuel consumption
Natural Gas ft³/hr (m³/hr)
1/2 Load
Full Load
Liquid Propane ft
3
/hr (gal/hr) [L/hr]
1/2 Load
Full Load
73 (2.07)
117 (3.31)
31.6 (0.87) [3.29]
51.6 (1.42) [5.37]
Note: Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet at all load ranges - 5–7 in water column (1.24–1.74 kPa) for NG, 10–12 in water column (2.49–2.99 kPa)
for LP gas. For BTU content, multiply ft
3
/hr x 2500 (LP) or ft
3
/hr x 1000 (NG). For Megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG).
Controls
LED indicators Simple user interface for ease of operation.
Mode buttons: AUTO Automatic start on utility failure. 7 day exerciser.
OFF Stops unit. Power is removed. Control and charger still operate.
MANUAL/TEST (start) Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Engine start sequence Cyclic cranking: Engine cranks a maximum of five times at factory set intervals and durations.
Engine warm-up 6 sec (30 sec with Cold Smart Start)
Engine cool-down 1 min
Starter lock-out Starter cannot re-engage until five seconds after engine has stopped.
2.5 amp Smart Battery Charger Standard
Automatic voltage regulator Standard
Automatic low oil level shutdown Standard
Overspeed/Underspeed shutdown Standard
High temperature shutdown Standard
Overcrank protection Standard
Safety fused Standard
Wiring error detection Standard
Battery problem warning Standard
Charger problem warning Standard
RPM Sensor Loss shutdown Standard
Maintenance indicators (indicate break-in and regular maintenance is due) Standard
Rating definitions - Optional Standby: Applicable for supplying backup power for the duration of the utility power outage with correct maintenance performed. No overload capability is available for this rating. (All
ratings in accordance with BS5514, ISO3046, UL2200, and DIN6271).
* Maximum kilovolt amps and current are subject to and limited by such factors as fuel BTU/megajoule content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases
approximately 3.5% for each 1,000 ft (304.8 m) above sea level; and also will decrease approximately 1% for each 10 °F (6 °C) above 60 °F (16 °C).
**Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters.
7.5 kW
SpecificationsPowerPact
®
System - 7.5 kW