Maintenance
52 MTP4000-6000DZV/DZD Operating Manual 31609 A
Changing the Oil Filter
Note: The filter cartridge should never be pre-filled. There is a danger of dirt contamination.
1. Loosen and unscrew the filter with filter tool. Refer to engine manual for more information.
2. Collect the draining engine oil.
3. Clean the sealing surface of the filter support with a lint-free, clean cloth.
4. Oil the gasket of the new filter cartridge lightly.
5. Screw on the new filter by hand until the gasket is touching and then torque to 11-13 ft-lbs (15-17 Nm).
6. Fasten the twist protection clamps (optional).
RESETTING THE CANPLUS 750 CONTROLLER
1. Hold the far right button to enter the Configuration menu.
2. Enter password 4444.
3. Enter Display
4. Select service interval to change/reset.
Adjusting The Service Timers
Pressing button 4 allows adjusting the selected service timer. Refer to “Service Timers” on page 25 for more
information.
The top level Configuration menu and its six choices.
00351
Service Timers