Product Manual A
General Information
32 MTP4000-6000DZV/DZD Operating Manual 31609 A
Low Set Point
For Empty and Maintain Out modes, sets the level that ends an autostart cycle. For Fill and Maintain In modes, sets
the level that begins a cycle.
Dead Band
Sets the amount of change from the target point required to alter the engine speed.
Starter
This submenu configures starter control options for autostart.
Restart Attempts
Selects the number of times to attempt restart.
Restart Delay Sec
Selects the number of seconds to wait before attempting a restart.
Start on Sec
Selects the maximum number of seconds the starter can be engaged.
SETTINGS MENU
This submenu allows the user to configure CANplus hardware.
Governor
Selects between Elect (electronically governed) and Mech (mechanically gov-
erned) engines modes. For mechanically governed engines the CANplus I/O
Board functions as an ECU, broadcasting engine parameters such as oil pressure
and temperature on the CANbus.
Note: Switching governor modes requires cycling power before calibrating the
RPM. The CANplus Configurator must be used to configure mechanical engine
parameters.
CP750 CAN Add
Selects the address used by the display to communicate with the CANplus I/O Board. The default I/O Board address
is 128.
Note: Engine data is always transmitted using address 0 in mechanically governed mode.
WARNING
Incorrectly configuring the CP750 CAN Address prevents the display from receiving
I/O Board data for the display menus and can result in data collisions on the CANbus.
00373
00374