Product Manual A

General Information
31609 A MTP4000-6000DZV/DZD Operating Manual 31
Ramp Up/Down
This submenu configures the speed profile for automatic start/stop operation.
Warm Up s
Selects the number of seconds to operate at idle speed before beginning the ramp
to intermediate speed. The warm-up time begins when the starter is disengaged.
Ramp Up s
Selects the number of seconds to ramp from idle speed to intermediate speed after
warm-up.
Intermediate s
Selects the number of seconds to operate at intermediate speed before ramping to run speed.
Ramp to Run s
Selects the number of seconds to ramp from intermediate speed to run speed after intermediate warm-up.
Ramp Down s
Selects the number of seconds to ramp from current speed to idle speed. The ramp down time begins when the
automatic start/stop system detects a stop event.
Cool Down m
Selects the number of minutes to operate at idle speed after ramp down time. At the end of the cool down period,
the engine will be stopped.
Servo
Configures the servo profile for autostart maintain modes.
Gain
Controls the aggressiveness of the maintain servo modes.
Delay 10mS
Controls how quickly the maintain servo mode responds to changes in level.
Transducer
This submenu configures the transducer type and set points.
Type
Selects between Level and Pressure CANplus Configurator.
Range
Selects appropriate range for the transducer type.
High Set Point
For Empty and Maintain Out modes, sets the level that begins and autostart cycle. For Fill and Maintain In modes,
sets the level that ends the cycle.
Maintain Point
Sets the target point for maintain modes.