Product Manual A

General Information
16 MTP4000-6000DZV/DZD Operating Manual 31609 A
CONTROL PANEL
The CANplus
®
750 (CP750™) control panel is a universal platform to monitor, control and automatically start/stop
both electronically and mechanically governed diesel engines. The microprocessor-based, solid-state design uses
high power semiconductors instead of electromechanical relays to ensure reliable high current switching. Graphical
gauge pages or a single large analog gauge are displayed on the 4.25 in. (10.79 cm) diagonal Liquid Crystal Display
(LCD). Virtually any SAE J1939 parameter reported by the Engine Control Unit (ECU) can be displayed, including
Revolutions Per Minute (RPM), coolant temperature, oil pressure, engine hours, voltage and diagnostic codes. The
trans-reflective, backlit display is clearly readable in both bright sunlight and total darkness and is housed in a rugged
IP67-rated housing.
Current alarm conditions are displayed in plain language on pop-up messages and can be viewed in the alarm list.
Various diagnostic screens allow detailed investigation of the CANbus data stream. By accessing the Configuration
menu, users can customize displayed data to show metric or US units, display language and various other parameters
such as the full-scale reading of gauges. Four bright Light Emitting Diodes (LEDs) below the display indicate Auto
Standby, Preheat, Stop and Warning status.
Five buttons access a context dependent button bar when any button from 1 to 4 is pressed. The graphical menu
structure uses icons to indicate the button’s current function. After five seconds of inactivity, the button bar disappears.
Note: Most problems with electronically controlled engines can be pinpointed via ECU diagnostic messages. Use
the display or ECU diagnostic tool to view fault codes. Engine state information and diagnostic codes displayed by
the CANplus display are provided via the CANbus.
Automatic Operation
The CP750™ panel features advanced automatic start/stop controls which can meet almost any requirement. Two
Button 1 Button 2 Button 3 Button 4 Button 5
Analog Gauge
Pages
Press repeatedly to
cycle through four
pages of analog
gauges (16 total).
Digital Gauge
Pages
Press repeatedly to
cycle through four
pages of digital
gauges (16 total).
Single Analog
Gauge
Press repeatedly to
cycle through avail-
able analog
gauges.
Active Alarm Page
Displays active
alarms with a plain
language descrip-
tion.
Gauge Adjust
Configures the
parameters dis-
played by gauge
pages.
(Quad Adjust must
be enabled.)
00337
00332
00333
00338
00339
00332