Full Product Manual

General Information and Setup
Owner’s/Installation Manual for SMM 3
Section 2 General Information and Setup
Figure 2-1. Features and Controls
Know Your Smart Management Module and
Carton Contents
Priority Dial (A) – Sets module priority.
NOTE: PRIORITY MUST BE DIFFERENT for each module
in an installation. Priority sets the order in which loads recover
from a load shed event. Recovery time from a load shed event
is five minutes for Priority 1. Each priority after Priority 1 waits
an additional 15 seconds after the initial recovery time. See
Table 1.
Lockout Switch (B) – Prevents load from operating when sys-
tem is operating under generator power. See Table 2.
NOTE: Recovery time is based on priority dial settings. See
Table 1.
Test Button (C) – Disables contactor output for a specified
time.
LED (D) – Provides module status. See Table 3.
Contactor (E) – Controlled by a smart controller in module.
Contactor remains CLOSED until generator power is required.
Upon generator activation, controller moves to OPEN to handle
overload conditions.
NOTE: The contactor is also opened during lockout switch
ACTIVE state.
Mounting Holes (F) – Internal enclosure mounting holes pro-
vide clean and sturdy mounting.
Priority Decal (G) – Provided for recording priority of each
module in installation. Should be installed on electrical panel.
000106
A
B C
D
E
F
F
000143a
G
Table 1. Priority Dial Settings
Priority Recovery Time
1 5 minutes
2 5 minutes 15 seconds
3 5 minutes 30 seconds
4 5 minutes 45 seconds
5 6 minutes
6 6 minutes 15 seconds
7 6 minutes 30 seconds
8 6 minutes 45 seconds
9Not Used
0Not Used