Full Product Manual

Installation, Tests and Troubleshooting
Owner’s/Installation Manual for SMM 7
Section 3 Installation, Tests and Troubleshooting
Electrical Specifications
Enclosure Specifications
Remove Contents from Carton
1. Open carton.
2. Remove and verify carton contents.
3. Retain carton for mounting template.
Carton Contents:
Smart Management Module (SMM)
Priority decal
Owner/Installation manual
4. Contact the place of purchase with the unit model num-
ber for any missing carton contents.
5. Record date of purchase on front cover of this manual.
Tools Needed For Installation
Power drill and suitable drill bit
Phillips and flat head screwdrivers
Mounting screws or wall anchors
Electrical materials
Mounting Instructions
The recommended installation is near the electrical panel or
appliance/load. The enclosure has a UL type 3R rating and can
be mounted indoors or outdoors. It provides a degree of
protection against rain and sleet and is undamaged by the
formation of ice on the enclosure.
1. Turn OFF both UTILITY (NORMAL) and EMERGENCY
(STANDBY) power supplies.
2. Choose mounting location (near electrical panel,
appliance or load to be managed).
3. Use a flat head screwdriver to remove appropriate
knockouts from module enclosure for wiring. See A in
Figure 3-1.
NOTE: If outdoor installation is chosen, bottom knockouts
must be used to meet NEMA 3R rating and protect against
water ingress.
4. Hold SMM enclosure against mounting surface with
arrows pointing up, and mark or drill four mounting holes.
See B in Figure 3-1 for arrows.
5. Install SMM enclosure to mounting surface using appro-
priate mounting screws or wall anchors.
Figure 3 -1. Knockouts and UP Arrows
Figure 3 -2. Mounting Dimensions
Input Voltage 240 VAC
Current Rating 50A resistive, 40A inductive
Locked Rotor Amp Rating 240A
Motor Rating 3HP
Contactor Coil Voltage 240 VAC
UL Rating Type 3R
Temperature -30 to 50 deg C (-22 to 122 deg F)
(000116)
DANGER
Electrocution. Turn utility and emergency
power supplies to OFF before connecting power
source and load lines. Failure to do so will result
in death or serious injury.
Height (in/mm)
H1 6.17/156.8
H2 2.36/60
Width (in/mm)
W1 7.06/179.4
W2 4.72/120
Depth (in/mm) D1 3.7/94
000138
A
A
A
B
W1
W2
H2H1
D1
000107