Product Manual
Section 4: Operation
12 Homelink Upgradeable Manual Transfer Switch Owner’s Manual
Shutting Generator Down While
Under Load
IMPORTANT NOTE: To turn the generator OFF
during utility outages to perform maintenance, or
conserve fuel, follow these important steps:
To turn the generator OFF (while running in AUTO and
Online):
1. Turn the main utility disconnect OFF.
2. Turn the main line circuit breaker (MLCB) on the
generator to OFF (OPEN).
3. Turn the generator OFF.
NOTE: If turning the unit off for longer than 24 hours,
remove the F1 fuse from the generator controller.
To turn the generator ON:
1. Reinstall F1 fuse if necessary.
2. Put the generator back into AUTO and allow to
start and warm-up for a few minutes.
3. Set the MLCB on the generator to ON.
The system will now be operating in automatic mode. The
main utility disconnect can be turned ON (CLOSED).
NOTE: To shut the unit off, this complete process must
be repeated.
Figure 4-2.
A. Rocker Button (Utility or Generator Selector)
B. Utility Light (Loads are on Generator, but Utility is Available)
C. Generator Power Light (Generator is On)
D. Circuit Breakers
E. Screws
000142
E
E
C
E
D
A
B
E