Install Manual

Cold Weather Kit - PowerPactâ„¢ Model No. 006808-1
Figure 5.
13. Run and tie wrap harness extension to existing wiring harness,
and connect. (See Figure 6).
NOTE: Battery heater (P) and block heater (Q) require 240 VAC to
operate. Breather heater needs 120 VAC to operate.
Figure 6.
14. Run harness extension through control box and plug into 240 VAC
input sense terminal block, N1 (S) and N2 (R) on the Terminal
Block (O). (See Figures 6 and 7).
NOTE: N1 and N2 do not have specific connection designations.
Connect either wire to N1 or N2.
Figure 7.
15. Run wires from breather heater and connect one leg to terminal
block T1 (T) and the other leg to the neutral bar (U). (See Figure
8). Tie wrap to secure the wires.
NOTE: Breather heater wires do not have specific polarity designa-
tion. Connect either wire to T1 and Neutral Bar.
16. Verify wire routing to ensure wires will not be pinched or cut. Use
tie wraps where necessary.
Figure 8.
17. Connect battery bracket and battery cables. Secure the cover on
positive battery post after securing cables.
Important: Verify that breather heater wires are correctly con-
nected to T1 and Neutral Bar. Do not connect breather heater wires
to N1 & N2. Wiring 120 VAC wires to 240 VAC supply will damage
the heater.
NOTE: When connecting battery cables, connect positive (red) cable
first.
18. Install battery access panel and secure to engine divider panel.
19. Install back panel. Ensure rubber bellows is secured around plastic
collar in back panel.
20. Install front access panel, followed by roof panel.
21. Secure all panels with appropriate fasteners removed previously.
22. Install electrical access panel and ensure grounding wire con-
nected to panel is securely attached to grounding terminal block.
23. Install 7.5A fuse..
24. Connect utility inputs to unit at transfer switch.
25. Set unit to desired mode and secure roof panel with appropriate
fasteners.
000591
N
000592
Q
O
P
R
S
T1
NEUTRAL
N2
N1
000594
T U
(000133)
WARNING
Explosion. Batteries emit explosive gases.
Always connect positive battery cable first to
avoid spark. Failure to do so could result in
death or serious injury.
(000129)
DANGER
Electrocution. High voltage is present at transfer
switch and terminals. Contact with live terminals
will result in death or serious injury.
(000135)
CAUTION
Engine damage. Verify proper type and quantity of
engine oil prior to starting engine. Failure to do so
could result in engine damage.
Part No. 0L2621 Rev A 04/02/2015 Printed in USA
© Generac Power Systems, Inc. All rights reserved
Specifications are subject to change without notice.
No reproduction allowed in any form without prior written
consent from Generac Power Systems, Inc.
Generac Power Systems, Inc.
S45 W29290 Hwy. 59
Waukesha, WI 53189
1-888-GENERAC (1-888-436-3722)
www.generac.com