Installation Guide

Electrical Connections
28 Installation Guidelines for Air-Cooled Generators
Figure 6-1. Control Wiring (Behind Control Board)
NOTE: Wires 23, 194 and 0 must be run through the provided wire shielding provided in the manual bag to sep-
arate the low voltage from the high voltage wires unless the requirement of 300.3(c)(1) of the NEC are met (see
the Parts Shipped Loose section).
NOTE: Must be connected to keep battery charged whether unit is running or not.
6.3 — Main AC Wiring
Figure 6-2. Main AC Wiring
NOTE: Main AC (E1, E2 and Neutral) wiring must be in accordance with local jurisdiction and codes.
LARGE NEUTRAL LUG TORQUE SPEC
2/0 TO 14AWG 120 IN-LB (13.56 N-M)
4-6 AWG 35 IN-LB (3.95 N-M),
8 AWG 25 IN-LB (2.82 N-M),
10-14 AWG 20 IN-LB (2.26 N-M)
LARGE GROUND LUG TORQUE SPEC
2/0 TO 14AWG 120 IN-LB (13.56 N-M)
SPRING LOADED CONNECTION POINTS
A
C
D
E
OPTIONAL ALARM
RELAY CONTACTS
(Normally Open)
B*
(*see note below)