Specification
4 of 5
8/11 kW
8/11 kW switch options
®
Model 006237-0 (8 kW) 006437-1 (11 kW)
No. of Poles 2 2
Current Rating (Amps) 50 50
Voltage Rating (VAC) 250 250
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
80%
60%
80%
60%
Return to Utility* approx. 15 sec approx. 15 sec
Exerciser weekly for 12 minutes* Standard Standard
UL Listed Standard Standard
Total of Pre-wired Circuits
No. 15 A 120 V
No. 20 A 120 V
No. 20 A 240 V
No. 30 A 240 V
No. 40 A 240 V
No. 50 A 240 V
10
3
3
1
1
-
-
12
5
3
-
1
1
-
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts
10,000 10,000
Pre-Wired Switch Features
• Electrically operated, mechanically-held contacts
for fast, positive connections.
• Rated for all classes of load, 100% equipment
rated, both inductive and resistive.
• 2 pole, 250 VAC contactors.
• 30 millisecond transfer time.
• Single coil design.
• Main contacts are silver plated or silver alloy to
resist welding and sticking.
• NEMA 1 (indoor rated) enclosure is standard on
the pre-wired switch.
• Pre-wired 30 foot (9.1 meter) whip to connect to
the provided 5 foot pre-wired whip and external
connection box.
• Pre-wired 2 foot (0.61 meter) whip, color coded to
connect into the existing electrical panel.
Mechanical Dimensions
Height Width
Depth
H1 H2 H3 W1 W2 W3
in 18.5 22.5 22 10.5 15.4 14.4 3.8
mm 470 571.8 558.8 266.7 392 366 97.5
Wire Ranges
Conductor Lug Neutral Lug Ground Lug
1/0 - #14 2/0 - #14 2/0 - #14
Dimensions
Dimensions
Service Rated Switch Features
available on 11 kW model only
• Electrically operated, mechanically-held contacts for fast, clean connections.
• Rated for all classes of load, 100% equipment rated, both inductive and resistive.
• Service equipment rated, dual coil design.
• Rated for both aluminum and copper conductors.
• NEMA/UL 3R aluminum outdoor enclosure.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
Model 006438-2 (11 kW)
No. of Poles 2
Current Rating (Amps) 200
Voltage Rating (VAC) 250
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
80%
60%
Return to Utility* approx. 13 sec.
Exercise weekly for 12 minutes* Standard
UL Listed Standard
Enclosure Type NEMA/UL 3R
Withstand Rating (Amps) 22,000
Lug Range 250 MCM - #6
H2
DEPTH
H1
W2
W1
200 Amps 120/240, 1ø
Open Transition Service Rated
Height Width
Depth
H1 H2 W1 W2
in 27.24 30.0 11.4 13.5 7.09
mm 692.0 762.4 289.0 343.0 180.0
*Function of Evolution Controller
Note: The 50 amp switch is flush mountable. H1 and W1 refer to mounting hole spacing.
H2 and W2 are cover dimensions. H3 and W3 are the enclosure dimensions without cover.
*Function of Evolution Controller
H1
W1
W2
H2
50 Amp Switch