Product Manual

Installation
4 Transfer Switch Installation Guidelines
2.3 — Specifications
NOTE: If Ground Fault Circuit Interrupting (GFCI) breakers, Arc-Fault breaker or surge protecting circuit breakers are used in the trans-
fer switch, they will reduce the maximum number of circuits from the number shown in the table above. Also if circuit breakers larger
than 50 amps are used as sub-feed breakers, the maximum number of circuit breakers will also be reduced. Contact your local installer
or dealer for more information on GFCI, Arc-Fault and Surge Protecting circuit breakers.Because GFCI and AFCI circuit breakers can
take up more than one space, the overall maximum number of circuits may be reduced from the number shown.
2.4 — Installation Procedure
HAZARDOUS VOLTAGES ARE PRESENT INSIDE TRANSFER SWITCH ENCLOSURES THAT CAN CAUSE DEATH
OR SEVERE PERSONAL INJURY. FOLLOW PROPER INSTALLATION, OPERATION AND MAINTENANCE PROCE-
DURES TO AVOID HAZARDOUS VOLTAGES.
TURN OFF THE MAIN CIRCUIT BREAKER IN THE LOAD CENTER BEFORE STARTING INSTALLATION.
Table 1: SPECIFICATIONS
Model 6382 6335
UTILITY MAIN breaker, Included 200 Amp 200 Amp
GEN MAIN breaker, included 30 Amp 50 Amp
Max Load per Circuit As marked As marked
Max Load on Generator 30 Amp 50 Amp
Max Watts @ 250 Volt 7500 12,500
Max Watts @ 125 Volt 7500 12,500
Max 1-pole Circuits * 12 12
Max 2-pole Circuits * 66
NEMA Configuration of Power Inlet L14-30 CS6365
Voltage 125/250 Volts 125/250 Volts
NEMA Type Enclosure 3R – Outdoor 3R – Outdoor
Phase 11
Minimum Gauge / Cord Size 10/4 6/4
+