Dimensions Guide

4 of 5
8/11/13kW
8/11/13kW switch options
Model 006251-0 (8 kW) Model 006440-0 (11 kW) Model 006254-0 (13 kW)
No. of Poles 2 2 2
Current Rating (Amps) 50 50 100
Voltage Rating (VAC) 120/240, 1Ø 120/240, 1Ø 120/240, 1Ø
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
80%
60%
80%
60%
80%
60%
Return to Utility* approx. 15 sec. approx. 15 sec. approx. 15 sec.
Exercise weekly for 12 minutes* Standard Standard Standard
UL Listed Standard Standard Standard
Total of Pre-wired Circuits
No. 15A 120V
No. 20A 120V
No. 20A 240V
No. 30A 240V
No. 40A 240V
No. 50A 240V
10
3
3
1
1
-
-
12
5
3
-
1
1
-
14
4
6
1
-
1
-
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts
10,000 10,000 10,000
Pre-Wired Switch Features
Electrically operated, mechanically-held contacts for
fast, positive connections.
Rated for all classes of load, 100% equipment rated,
both inductive and resistive.
• 2 pole, 250 VAC contactors.
• 30 millisecond transfer time.
• Dual coil (100A) and single coil (50A) designs.
Main contacts are silver plated or silver alloy to
resist welding and sticking.
NEMA 1 (indoor rated) enclosure is standard on the
pre-wired switch.
Pre-wired 30 foot (9.1 meter) whip to connect to
the provided 5 foot pre-wired whip and external
connection box.
Pre-wired 2 foot (0.61 meter) whip, color coded to
connect into the existing electrical panel.
Wire Ranges
Amps Conductor Lug Neutral Lug Ground Lug
50 1/0 - #14 2/0 - #14 2/0 - #14
100 2/0 - #14 2/0 - #14 2/0 - #14
H1
W1
W2
H2
Dimensions
Dimensions
Smart Switch Features
available on 11 & 13kW models only
• Includes Digital Power Management Technology standard (DPM).
• Intelligently manages two air conditioner loads with no additional hardware.
Up to four more large (240V) loads can be managed when used in conjunction with
Power Management Modules (PMM**).
Electrically operated, mechanically-held contacts for fast, clean connections.
Rated for all classes of load, 100% equipment rated, both inductive and resistive.
• 2 pole, 250 VAC contactors.
• Service equipment rated, dual coil design.
• Rated for both aluminum and copper conductors.
• NEMA/UL 3R aluminum outdoor enclosure.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
**Note: PMM starter kit is required prior to using the modules.
Model 006441-0 (11kW) / 006255-0 (14kW)
No. of Poles 2
Current Rating (Amps) 200
Voltage Rating (VAC) 120/240, 1Ø
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
80%
60%
Return to Utility* approx. 13 sec.
Exercise weekly for 12 minutes* Standard
UL Listed Standard
Enclosure Type NEMA/UL 3R
Withstand Rating (Amps) 10,000
Lug Range 250MCM - #6
H2
DEPTH
H1
W2
W1
200 Amps 120/240, 1ø Open Transition Service Rated
Height Width
Depth
H1 H2 W1 W2
Inches 27.24 30.0 11.4 13.5 7.09
mm 692.0 762.4 289.0 343.0 180.0
*Function of Evolution Controller
*Function of Evolution Controller
Mechanical Dimensions
Amps
Height Width
Depth
H1 H2 H3 W1 W2 W3
50*
18.5 in. 22.5 in. 22 in. 10.5 in. 15.4 in. 14.4 in. 3.8 in
470mm 571.8mm 558.8mm 266.7 392mm 366mm 97.5mm
100
23.5 in. 26.4 in. N/A 8.3 in. 12.6 in. N/A 6.3 in.
597mm 671.7mm N/A 211mm 320.7mm N/A 159.6mm
H1
W1
W2
H2
50 Amp Switch
100 Amp Switch
*Note: The 50 Amp switch is flush mountable. H1 and W1 refer to mounting hole spacing.
H2 and W2 are cover dimensions. H3 and W3 (not shown in diagram) are the enclosure
dimensions without cover.