Full Product Manual
Table Of Contents
- Owner's Manual
- Table of Contents
- INTRODUCTION
- READ THIS MANUAL THOROUGHLY
- SAFETY RULES
- General Information
- Operation
- 2.1 KNOW THE GENERATOR
- 2.2 HOURMETER
- 2.3 CONNECTION PLUGS
- 2.4 HOW TO USE THE GENERATOR
- 2.5 DON’T OVERLOAD THE GENERATOR
- 2.6 WATTAGE REFERENCE GUIDE
- 2.7 BEFORE STARTING THE GENERATOR
- 2.8 STARTING PULL START ENGINES
- 2.9 STARTING ELECTRIC START ENGINES
- 2.10 STOPPING THE ENGINE
- 2.11 LOW OIL LEVEL SHUTDOWN SYSTEM
- 2.12 CHARGING THE BATTERY (ELECTRIC START UNITS ONLY)
- Maintenance
- Troubleshooting
- Notes
- Manual Part No. 0K0172
- Manual del propietario
- Índice
- INTRODUCCIÓN
- LEA ESTE MANUAL MINUCIOSAMENTE
- REGLAS DE SEGURIDAD
- Información general
- Funcionamiento
- 2.1 CONOZCA EL GENERADOR
- 2.2 HORÓMETRO
- 2.3 ENCHUFES DE CONEXIÓN
- 2.4 CÓMO USAR EL GENERADOR
- 2.5 NO SOBRECARGUE EL GENERADOR
- 2.6 GUÍA DE REFERENCIA DE POTENCIA EN WATTS
- 2.7 ANTES DE ARRANCAR EL GENERADOR
- 2.8 ARRANQUE DE MOTORES CON CABLE DE ARRANQUE
- 2.9 ARRANQUE DE MOTORES CON ARRANQUE ELÉCTRICO
- 2.10 PARADA DEL MOTOR
- 2.11 SISTEMA DE APAGADO POR NIVEL DE ACEITE BAJO
- 2.12 CARGA DE LA BATERÍA (UNIDADES CON ARRANQUE ELÉCTRICO SOLAMENTE)
- Mantenimiento
- Resolución de problemas
- Notas
- Manual Parte No. 0K0172
- Manuel d'entretien
- Table des matières
- INTRODUCTION
- LIRE ATTENTIVEMENT CE MANUEL
- RÈGLES DE SÉCURITÉ
- Informations générales
- Fonctionnement
- 2.1 CONNAÎTRE LE GÉNÉRATEUR
- 2.2 HOROMÈTRE
- 2.3 PRISES DE CONNEXION
- 2.4 COMMENT UTILISER LA GÉNÉRATRICE
- 2.5 NE PAS SURCHARGER LA GÉNÉRATRICE
- 2.6 GUIDE DE RÉFÉRENCE DE WATTAGE
- 2.7 AVANT DE DÉMARRER LA GÉNÉRATRICE
- 2.8 DÉMARRER LES MOTEURS À DÉMARRAGE MANUEL
- 2.9 DÉMARRER LES MOTEUR À DÉMARRAGE ÉLECTRIQUE
- 2.10 ARRÊTER LE MOTEUR
- 2.11 SYSTÈME D'ARRÊT DE NIVEAU BAS D'HUILE
- 2.12 CHARGER LA BATTERIE (APPAREILS À DÉMARRAGE ÉLECTRIQUE SEULEMENT)
- Entretien
- Dépannage
- Remarques
- Manuel, référence 0K0172

7
Figure 6 - 120 Volt AC, 20 Amp, Duplex Receptacle
2.3.2 120 VAC, 20 AMP, GFCI DUPLEX RECEPTACLE
(CARB ONLY)
This is a 120 Volt outlet protected against overload by a 20 Amp
push-to-reset circuit breaker (Figure 6A). Use each socket to
power 120 Volt AC, single phase, 60 Hz electrical loads requiring
up to a combined 2400 watts (2.4 kW) or 20 Amps of current. Use
only high quality, well-insulated, 3-wire grounded cord sets rated
for 125 Volts at 20 Amps (or greater).
Keep extension cords as short as possible to prevent voltage drop
and possible overheating of wires.
Figure 6A - 120 Volt AC, 20 Amp, GFCI Duplex
Receptacle
2.3.3 120/240 VAC, 30 AMP RECEPTACLE
Use a NEMA L14-30 plug with this receptacle (rotate to lock/
unlock). Connect a suitable 4-wire grounded cord set to the plug
and to the desired load. The cord set should be rated for 250 Volts
AC at 30 Amps (or greater) (Figure 7).
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase
loads requiring up to 3600 watts (3.6 kW) of power at 30 Amps
or 240 Volt AC, 60 Hz, single phase loads requiring up to 7200
watts (7.2 kW) of power at 30 Amps. The outlet is protected by
two 25 Amp (5.5kW) or two 30 Amp (6.5kW) push-to-reset or one
30 Amp 2-pole toggle switch or two 30 Amp push button to reset
(6.5/7.5kW) circuit breaker.
Figure 7 - 120/240 VAC, 30 Amp Receptacle
2.4 HOW TO USE THE GENERATOR
See the "To Start the Engine" section for how to safely start and
stop the generator and how to connect and disconnect loads. If
there are any problems operating the generator, please call the
generator helpline at 1-888-436-3722.
Never operate in an enclosed area or indoors!
NEVER use in the home, in a vehicle, or in
partly enclosed areas such as garages, EVEN
IF doors and windows are open! ONLY use
outdoors and far from open windows, doors,
vents, and in an area that will not accumulate
deadly exhaust.
The engine exhaust fumes contain carbon
monoxide, which you cannot see or smell.
This poisonous gas, if breathed in sufficient
concentrations, can cause unconsciousness or
even death.
Adequate, unobstructed flow of cooling and
ventilating air is critical to correct generator
operation. Do not alter the installation or permit
even partial blockage of ventilation provisions,
as this can seriously affect safe operation
of the generator. The generator MUST be
operated outdoors.
This exhaust system must be properly
maintained. Do nothing that might render the
exhaust system unsafe or in noncompliance
with any local codes and/or standards.
Always use a battery operated carbon
monoxide alarm indoors, installed according to
the manufacturer's instructions.
Operation