Specification

3 of 4
**Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters. Rating definitions - Standby: Applicable
for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). * Maximum
wattage and current are subject to and limited by such factors as fuel Btu/megajoule content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for
each 1,000 feet (304.8 meters) above sea level; and also will decrease about 1 percent for each 6 °C (10 °F) above 16 °C (60 °F).
Generator
Model 005818-0 (6 kW)
Rated Maximum Continuous Power Capacity (LP) 6,000* Watts
Rated Voltage 120 VAC (240 VAC capable w/ kit 006016-1)
Rated Maximum Continuous Load Current – 120 Volts 50 (25 @ 240 VAC)
Main Line Circuit Breaker 50 Amp (25 after conversion)
Phase 1
Number of Rotor Poles 2
Rated AC Frequency 60 Hz
Power Factor 1.0
Battery Requirement (not included) Group 26R, 12 Volts and 525 CCA Minimum
Unit Weight (lb/kg) 387/175.5
Dimensions (L x W x H) in/mm 48 x 25 x 29/1218 x 638 x 732
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load** 52
Engine
Type of Engine GENERAC OHVI
Number of Cylinders 2
Displacement 530 cc
Cylinder Block Aluminum w/ Cast Iron Sleeve
Valve Arrangement Overhead Valve
Ignition System Solid-state w/ Magneto
Governor System Electronic
Compression Ratio 9.5:1
Starter 12 Vdc
Oil Capacity Including Filter 1.7 qt/1.6 L
Oil Reservoir Capacity 4.2 qt/4.0 L
Operating rpm 2,600
Fuel Consumption
Liquid Propane ft
3
/hr (gal/hr) [l/hr]
1/2 Load
Full Load
27.6 (0.76) [2.87]
56.4 (1.55) [5.87]
Note: Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet at all load ranges - 10-12" water column (19-22 mm mercury) for LP gas.
For Btu content, multipy ft
3
/hr x 2500
Controls
2-Line Plain Text LCD Display Simple user interface for ease of operation.
Mode Switch: Auto Puts unit in standby mode, waiting for inverter start call.
Off Stops unit. Power is removed. Control and charger still operate.
Manual/Test (start) Start with starter control, unit stays on.
Starter Lock-out Starter cannot re-engage until 5 sec. after engine has stopped.
2.5 Amp Smart Battery Charger Standard
Automatic Voltage Regulator w/ Overvoltage Protection Standard
Automatic Low Oil Pressure Shutdown Standard
Overspeed Shutdown Standard, 72 Hz
High Temperature Shutdown Standard
Overcrank Protection Standard
Safety Fused Standard
Low Battery Protection Standard
50 Event Run Log Standard
Internal Fault Protection Standard
EcoGen™ - 6 kW specifications
6 kW
®