Air-Cooled Instruction Sheet
Engine Shutdown Add-On Kit 5
Firmware Update—Evolution 1.0
(if required)
The generator controller may require a firmware update.
For EcoGen™ and Synergy™ generators, firmware
version 1.14 or higher is required. For all other
generators with Evolution or Sync 2.0 controllers, version
1.18 or higher is required.
Verify controller firmware version. If an update is
required, install latest version before testing engine
shutdown switch(es).
1. With generator controller OFF, enter Edit menu.
2. Scroll through the options and select “Update
Firmware.” Press Enter.
3. Insert a USB drive with current firmware into
controller port. Follow prompts.
4. After firmware has been updated, press “Escape”
until sub menu screen displays.
Activate Engine Shutdown
Functionality (Evolution 1.0 only)
Verify firmware version of the controller is correct as
specified in Firmware Update—Evolution 1.0 (if
required). If an update is required, download and install
the latest firmware before proceeding.
The controller must detect the installed switch to activate
engine shutdown functionality.
1. Verify controller is powered and in the Off mode.
2. Turn switch(es) ON to verify switch(es) are engaged
(closed).
3. Turn switch OFF. The controller should recognize
that the switch has been disengaged and display
“Auxiliary Shutdown Alarm.”
• If alarm appears on controller screen, turn switch
ON and clear alarm
• If alarm does not appear on controller screen,
engine shutdown is not functioning. Verify firmware
version meets requirements. Disconnect power
and re-check wiring installation. Contact Generac
Technical Support if the problem cannot be
identified or if you need assistance.
Test Switch Operation
Test engine shutdown switch(es) after installation to
verify proper operation.
1. Verify switch(es) are ON.
2. Use controller to manually start generator.
3. With engine running, turn one switch OFF. Engine
should shut down immediately.
• If engine stops, turn switch ON, clear alarm on
controller, and restart engine to verify generator is
operating normally. After verifying normal operation
of first switch, verify operation of second switch, if
installed.
• If engine does not stop, switch is not functioning
correctly. Stop generator through the control panel,
and re-check wiring installation. Contact Generac
Technical Support if the problem cannot be
identified or if you need assistance.
4. Show homeowner how to operate the engine
shutdown switch. Remind him or her that the engine
shutdown switch is not intended to be the primary
means to shut down the generator under normal
operating conditions. Accidental activation of an
engine shutdown switch will prevent the generator
from operating during a power outage.
Complete Installation
To turn generator back ON:
1. Move generator main line circuit breaker (generator
disconnect) to ON (Closed).
2. Place controller in AUTO.
3. Close lid.
(000135)
CAUTION
Engine damage. Verify proper type and quantity of
engine oil prior to starting engine. Failure to do so
could result in engine damage.
Part No. 10000013565 Rev B 5/9/17
©2017 Generac Power Systems, Inc. All rights reserved
Specifications are subject to change without notice.
No reproduction allowed in any form without prior written
consent from Generac Power Systems, Inc.
Generac Power Systems, Inc.
S45 W29290 Hwy. 59
Waukesha, WI 53189
1-888-GENERAC (1-888-436-3722)
www.generac.com