Product Manual
Installation Manual for SnapRS 9
Troubleshooting
Section 4: Troubleshooting
(000667)
Equipment damage. Never open a Generac SnapRS device.
Generac SnapRS devices are factory-sealed and contain
no field-servicable parts. Opening a Generac SnapRS device
could result in equipment damage.
CAUTION
There are no functional tests that can be performed on
SnapRS devices in the field. However, some simple
digital multimeter (DMM) checks can confirm the general
health of a SnapRS device.
DMM Red to SnapRS +, DMM Black to SnapRS –
Resistance reads ~ 300 kΩ to 350 kΩ
Diode check reads ~ 0.50 V to 0.55 V
DMM Red to SnapRS –, DMM Black to SnapRS +
Resistance reads ~ 12 MΩ