Install Manual
Location and Compliance
12 Installation Manual for Generac PWRcell Battery
Compliance
(000190)
DANGER
Loss of life. Property damage. Installation must
always comply with applicable codes, standards, laws
and regulations. Failure to do so will result in death
or serious injury.
WARNING
Electrocution. Refer to local codes and standards for
safety equipment required when working with a live
electrical system. Failure to use required safety
equipment could result in death or serious injury.
(000257)
(000182a)
WARNING
Equipment damage. Only qualified service personnel may
install, operate, and maintain this equipment. Failure to
follow proper installation requirements could result in death,
serious injury, and equipment or property damage.
Follow all instructions included in this manual and use
appropriate practices for all product wiring and installa-
tion.
NOTE: It is the responsibility of the installer to ensure
conformance with NFPA70E, Article 120, lockout/tagout
procedures. If the PWRcell inverter is installed out of
sight of the AC distribution panel, a correctly rated dis-
connect switch must be installed within sight of the PWR-
cel inverter. In the situation where the PWRcell inverter is
installed out of sight of the PWRcell battery product, a
correctly rated DC disconnect switch must be installed
within sight of the PWRcell battery.
Note on DC Wiring and the NEC
Some electricians or installers may be unfamiliar with DC
wiring in a residential setting. Note the following:
• NEC 215.12(C)(2) for correct DC wiring coloring.
• NEC 210.5(C)(2) for identification of DC conduc-
tors carrying more than 50V.
Always adhere to applicable codes when marking and
installing DC conductors.
See Table 3-2. For all REbus DC wiring observe the fol-
lowing coloring convention:
Table 3-2. REbus DC Wiring Coloring Convention
Wire Color
REbus + (RE+) Red
REbus - (RE-) Black or Blue
Ground (GND) Green or bare
NOTE: Mark or flag all conductors as appropriate.