Spec Sheet
3 of 11
®
GENERATOR OUTPUT VOLTAGE/kW - 60 Hz
kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both)
RG10090
120/240 V, 1Ø, 1.0 pf
96
400 96 400 400
120/208 V, 3Ø, 0.8 pf
100
347 96 333 400
120/240 V, 3Ø, 0.8 pf
100
300 96 288 350
277/480 V, 3Ø, 0.8 pf
100
150 96 144 175
RG13090
120/240 V, 1Ø, 1.0 pf
130 542
130 542 600
120/208 V, 3Ø, 0.8 pf
130 451
130 451 500
120/240 V, 3Ø, 0.8 pf
130 391
130 391 400
277/480 V, 3Ø, 0.8 pf
130 195
130 195 225
RG15090
120/240 V, 1Ø, 1.0 pf
134 558 144 600 700
120/208 V, 3Ø, 0.8 pf
140 486 150 520 600
120/240 V, 3Ø, 0.8 pf
140 421 150 451 500
277/480 V, 3Ø, 0.8 pf
140 210 150 226 250
operating data100 / 130 / 150 kW
ENGINE FUEL CONSUMPTION
Natural Gas Propane
(ft³ / hr) (m³ / hr) (ft³ / hr) (m
3
/ hr)
RG10090
25% of rated load 406 11.5 20 0.56
50% of rated load 655 18.5 294 8.3
75% of rated load 896 25.4 425 12.0
100% of rated load 1,128 31.9 528 15.0
RG13090
25% of rated load
635 18 270 7.6
50% of rated load
1,005 28.4 390 11.0
75% of rated load
1,401 39.7 516 14.6
100% of rated load
1,797 50.9 642 18.2
RG15090
25% of rated load
668 18.9 280 7.9
50% of rated load
1,127 31.9 430 12.2
75% of rated load
1,583 44.8 573 16.2
100% of rated load
2,042 57.8 720 20.4
SURGE CAPACITY IN AMPS
Voltage Dip
30%
RG10090
120 / 240 V, 1Ø 854
120 / 208 V, 3Ø 430
120 / 240 V, 3Ø 372
277 / 480 V, 3Ø 244
RG13090
120 / 240 V, 1Ø 854
120 / 208 V, 3Ø 816
120 / 240 V, 3Ø 707
277 / 480 V, 3Ø 351
RG15090
120 / 240 V, 1Ø 617
120 / 208 V, 3Ø 619
120 / 240 V, 3Ø 536
277 / 480 V, 3Ø 351
Note: Fu el pip e must b e siz ed f or ful l lo ad.
For Btu content, multiply ft³ / hr x 2,520 (LP) or ft³ / hr x 1,000 (NG).
For megajoule content, multiply m³ / hr x 93.15 (LP) or m³ / hr x 37.26 (NG).
Refer to “Emissions Data Sheets” for maximum fuel flow for EPA and SCAQMD
permitting purposes.
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no
overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Protector
®
Series