Spec Sheet

3 of 9
®
GENERATOR OUTPUT VOLTAGE/kW - 60 Hz
kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both)
RG048
120/240 V, 1Ø, 1.0 pf
48
200 48 200 200
120/208 V, 3Ø, 0.8 pf
48
167 48 167 175
120/240 V, 3Ø, 0.8 pf
48
144 48 144 150
277/480 V, 3Ø, 0.8 pf
48
72 48 72 80
RG060
120/240 V, 1Ø, 1.0 pf
60 250
60 250 300
120/208 V, 3Ø, 0.8 pf
60 208
60 208 200
120/240 V, 3Ø, 0.8 pf
60 180
60 180 200
277/480 V, 3Ø, 0.8 pf
60 90
60 90 100
RG080
120/240 V, 1Ø, 1.0 pf
75 312 80 333 400
120/208 V, 3Ø, 0.8 pf
75 260 80 278 300
120/240 V, 3Ø, 0.8 pf
75 226 80 241 300
277/480 V, 3Ø, 0.8 pf
75 113 80 120 150
operating data48 / 60 / 80 kW
ENGINE FUEL CONSUMPTION
Natural Gas Propane
(ft³ / hr) (m³ / hr) (gal / hr) (ft³ / hr) (l / hr)
RG048
Exercise cycle 101 2.86 0.67 24.5 2.54
25% of rated load 201 5.7 2.88 104.7 10.9
50% of rated load 336 9.5 4.16 151.3 15.7
75% of rated load 447 12.7 5.28 192 20
100% of rated load 604 17.1 6.61 240.4 25
RG060
Exercise cycle
103 2.9 0.9 33.2 3.5
25% of rated load
257 7.3 2.1 78 8.1
50% of rated load
432 12.2 4.4 161.2 16.8
75% of rated load
618 17.5 6.8 247.2 25.7
100% of rated load
808 22.9 8.4 305.6 31.8
RG080
Exercise cycle
103 2.9 0.9 33.2 3.5
25% of rated load
292 8.3 2.6 93.6 9.7
50% of rated load
534 15.1 5.7 208.8 21.7
75% of rated load
799 22.6 8.3 303.2 31.5
100% of rated load
1,063 30.1 10.8 393.2 40.9
SURGE CAPACITY IN AMPS
Voltage Dip @ < .4 pf
15% 30%
RG048
120 / 240 V, 1Ø 100 300
120 / 208 V, 3Ø 118 242
120 / 240 V, 3Ø 144 260
277 / 480 V, 3Ø 64 123
RG060
120 / 240 V, 1Ø 150 413
120 / 208 V, 3Ø 135 313
120 / 240 V, 3Ø 117 289
277 / 480 V, 3Ø 54 122
RG080
120 / 240 V, 1Ø 283 600
120 / 208 V, 3Ø 236 500
120 / 240 V, 3Ø 204 432
277 / 480 V, 3Ø 102 192
Note: Fu el pi pe m ust be s ize d f or fu l l l oa d.
For Btu content, multiply ft³ / hr x 2,520 (LP) or ft³ / hr x 1,000 (NG).
For megajoule content, multiply m³ / hr x 93.15 (LP) or m³ / hr x 37.26 (NG).
Refer to Emissions Data Sheets” for maximum fuel flow for EPA and SCAQMD
permitting purposes.
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage.
There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Protector
®