Brochure
4880kW PROTECTOR® SERIES
Automatic Standby Gaseous Generator
Generac Power Systems, Inc.
S45 W29290 Hwy. 59, Waukesha, WI 53189
www.Generac.com | 888-GENERAC (436-3722)
201902154 REV 06/20
©2020 Generac Power Systems. All rights reserved.
Specifications are subject to change without notice.
NATIONWIDE DEALER
SERVICE NETWORK
Generac’s commitment to service includes scheduled maintenance programs, warranty assistance and emergency service to ensure
that Generac customers are never left powerless. The largest nationwide dealer network has factory-trained technicians on staff and
maintains large inventories of Generac parts, components and accessories. Find a dealer near you at Generac.com.
SPECIFICATIONS (LP/NG) 48kW 60kW 80kW
Model Number RG04845 RG06045 RG08045
Output Amperage LP/NG 120/240 V, 1ø 1.0 pf 200/200 250/250 Contact Factory / 333
Output Amperage LP/NG 120/208 V, 3ø 0.8 pf 167/167 208/208 Contact Factory / 277
Output Amperage LP/NG 120/240 V, 3ø 0.8 pf 144/144 180/180 Contact Factory / 240
Output Amperage LP/NG 277/480 V, 3ø 0.8 pf 72/72 90/90 Contact Factory / 120
Engine/Alternator RPM 1800
Engine 4.5L, in-line 4-cyl. 4.5L Turbo, in-line 4-cyl. 4.5L Turbo, in-line 4-cyl.
Fuel Consumption @ full |oad - LPG cu. ft/hr (gal/hr) 240.4 (6.61) 305.6 (8.4) 393.2 (10.8)
Fuel Consumption @ full load - NG cu. ft/hr 604 808 1063
Quiet-Test Mode Ye s
db(A) at Exercise 68
db(A) Normal Operating Load 70 72 74
Dimensions (L” x W” x H”) 83 x 35 x 46 97 x 38 x 49 97 x 38 x 49
Generator Weight (lbs.) 1781 1912 2022
Mobile Link Connectivity Standard via Wi-Fi
Ethernet Module
Ye s
SCAQMD Model
• • •