Product Manual
Table Of Contents
- Section 1: Safety Rules & General Information
- Section 2: General Information
- Section 3: Activation and Startup
- Section 4: Operation
- Section 5: Maintenance
- Component Locations
- Access Panels
- Maintenance
- Remove From Service
- 25 Hour Break-In
- Daily Maintenance
- Schedule A Maintenance
- Schedule A Maintenance Item Locations
- Preliminary Instructions
- Inspecting the Enclosure Louvers
- Inspecting the Fuel Lines
- Inspecting Coolant Level and Hoses
- Inspecting Radiator for Clogging
- Checking Lubricating Oil Level and Drain Hose
- Replacing Lubricating Oil and Oil Filter
- Checking Battery Condition/Fluid Level
- Inspecting Accessory/Drive Belt
- Replacing Air Filter Element
- Final Instructions
- Schedule B Maintenance
- Schedule C Maintenance
- Return To Service
- Section 6: Troubleshooting
Maintenance
26 Owner’s Manual for Spark-Ignited Stationary Generators
Remove From Service
For safety, follow the steps below prior to inspection,
maintenance, or service.
IMPORTANT NOTE: If currently experiencing a utility
outage, see Removal From Service During Utility
Outage for special instructions.
1. Open viewing window. See Opening the Viewing
Window.
2. See Figure 5-5. Set generator MLCB (generator
disconnect) to OFF (OPEN) (A).
Figure 5-5. Generator Control Panel
3. Verify both auxiliary shutdown switches are OFF
(OPEN).
4. Press OFF on control panel (B). A red LED illumi-
nates to verify system is OFF.
5. Remove T1 fuse from transfer switch.
6. Pull up rubber flap (C) covering fuse holder and
remove 7.5 amp fuse.
7. Disconnect negative battery cable.
8. Place a DO NOT OPERATE tag or placard on both
the control panel and transfer switch.
9. If unit has been running, wait five minutes for
engine to cool.
25 Hour Break-In
Perform the following task:
• Replace lubricating oil and oil filter.
NOTE: See Replacing Lubricating Oil and Oil Filter
under Schedule A Maintenance.
Daily Maintenance
Perform the following tasks:
• Inspect enclosure louvers.
• Inspect fuel lines.
• Inspect coolant level and hoses.
• Inspect radiator for clogging.
• Inspect lubricating oil level and drain hose.
NOTE: See Inspecting the Enclosure Louvers through
Inspecting Coolant Level and Hoses under Schedule A
Maintenance.
(000130)
Accidental Start-up. Disconnect the negative battery
cable, then the positive battery cable when working
on unit. Failure to do so could result in death
or serious injury.
WARNING
o
OFF
PUSH TO TRIP
C
A
B
006374