Product Manual
Table Of Contents
- Section 1: Safety Rules & General Information
- Section 2: General Information
- Section 3: Activation and Startup
- Section 4: Operation
- Section 5: Maintenance
- Component Locations
- Access Panels
- Maintenance
- Remove From Service
- 25 Hour Break-In
- Daily Maintenance
- Schedule A Maintenance
- Schedule A Maintenance Item Locations
- Preliminary Instructions
- Inspecting the Enclosure Louvers
- Inspecting the Fuel Lines
- Inspecting Coolant Level and Hoses
- Inspecting Radiator for Clogging
- Checking Lubricating Oil Level and Drain Hose
- Replacing Lubricating Oil and Oil Filter
- Checking Battery Condition/Fluid Level
- Inspecting Accessory/Drive Belt
- Replacing Air Filter Element
- Final Instructions
- Schedule B Maintenance
- Schedule C Maintenance
- Return To Service
- Section 6: Troubleshooting
Activation and Startup
12 Owner’s Manual for Spark-Ignited Stationary Generators
Starting and Running Engine
Proceed as follows to start and run the engine:
1. See Figure 3-5. Pull up rubber flap covering fuse
holder and verify installation of 7.5 amp fuse (A).
Figure 3-5. Generator Control Panel
2. Set the main line circuit breaker (MLCB) (generator
disconnect) to OFF (OPEN) (B).
3. Verify both auxiliary shutdown switches are ON (I).
See Figure 3-6 for locations.
4. Press MANUAL on control panel (C) to start
engine. A blue LED illuminates to verify system is
in MANUAL.
5. Allow engine to run until it reaches normal operat-
ing temperature.
Press OFF on the control panel to stop the engine. A red
LED illuminates to verify system is OFF.
Display Reads:
Use Up arrow or Down arrow to select
either Yes or No.
Press ENTER.
Select YES to perform exercise at low speed. Select
NO to perform exercise at normal operating speed.
Display Reads:
Set Exercise Time.
Use Up arrow or Down arrow to
increment or decrement the hour. Press
ENTER.
Use Up arrow or Down arrow to
increment or decrement the minute.
Press ENTER.
Use Up arrow or DOWN arrow to scroll to
the day of the week. Press ENTER.
In AUTO, the engine starts and runs once each week at
the time and day specified. During the exercise cycle,
the unit runs approximately 12 minutes and then shuts
down. Transfer of loads to the generator does not
occur unless utility power fails.
Display Reads:
Fuel Type Selection.
Use UP or DOWN arrow to index the
correct fuel type.
Press ENTER.
Select the correct fuel based on the fuel
connected at the installation site.
Quiet Test Mode?
Yes No
Select Hour (0-23)
- 1 +
Fuel Selection
- LP +
- NG +
o
OFF
PUSH TO TRIP
006374
A
B
C