Product Manual

Maintenance
Owner’s Manual for Stationary Generators 41
Replace Air Filter Element
1. Remove wing nut (B), lock washer (C), and flat
washer (D) from threaded rod to release air cleaner
cover. See Figure 5-12.
2. Rem
ove the air filter element (A) and discard.
3. Th
oroughly clean air cleaner cover of any dust, dirt,
or debris.
4. Place ne
w air filter element against adapter flange.
NOTE: The air filter element is not
directional.
5. Insta
ll air cleaner cover (E) over threaded rod.
Install flat washer, lock washer and wing nut.
Tighten wing nut until snug.
A
A
B
C
D
E
Figure 5-12. Air Cleaner Cover and Filter Element
NOTE: Ser
vice kits are available from Independent
Authorized Service Dealers.
Final Instructions
If only performing Schedule A maintenance procedures,
proceed as follows:
1. Install
battery negative cable (black) onto battery
negative (-) terminal.
2. Install
left and right side access panels. See
Access Panels.
3. See Return To Service.
Schedule B Maintenance
NOTE: Perform Schedule B maintenance every two
years or after 250 hours of service, whichever comes
first. Before proceeding below, first perform all tasks
listed under Schedule A Maintenance.
NOTE: Th
e 2.4L (32 kW) unit is depicted in the artwork
used in this manual. For the general location of
components in all other models, see Schedule B
Maintenance Item Locations.
Schedule B Maintenance Item Locations
NOTE: The side of the enclosure with the viewing
window is identified as the rear of the generator set. The
right and left sides are identified by standing at the rear
and looking towards the front of the unit.
Model 22/27 kW 25/30 kW 32/38 kW 36/45 kW 48 kW 60 kW
Engine 2.4L 1.5L 2.4L 2.4L 5.4L 2.4L
Coolant Drain Hose
L R L L R L
Radiator Fill Cap
T T T T T T
Coolant Overflow Reservoir
L L L L L L
Spark Plugs
L R L L B L
R = Right Side L = Left Side B = Both Sides T = Top