Product Manual

Operation
24 Owner’s Manual for Stationary Generators
Alarm/Warning Conditions
The owner/operator is alerted to Alarm and/or Warning
conditions via the control panel LCD screen. All Alarm
conditions cause the generator to shut down.
The Warning messages alert the operator to conditions
th
at do not disable the unit or require immediate
correction.
The possible Alarm/Warning messages are listed below.
Alarm Messages Warning Messages
High Engine
Temperature
Low Oil Pressure
Overcrank
Overspeed
RPM Sense Loss
Underspeed
Controller Fault
Ignition Fault Code
Auxiliary Shutdown
WIRING ERROR
Over Voltage
Under Voltage
Overload
Canbus Error
Missing Cam Pulse
Missing Crank Pulse
Low Fuel Pressure
E-Stop
Low Battery
Exercise Set Error
Schedule A
Maintenance
Schedule B
Maintenance
Schedule C
Maintenance
Battery Problem
Charger Warning
Charger Missing AC
USB Warning
Download Failure
Check Engine
NOTE: Unle
ss properly trained to correct and clear
Alarm/Warning conditions, contact an IASD.
Change Time and Date
To change the time and date after activation, see the
Navigation Menu in Figure 4-3. If power is lost (battery is
d
isconnected/reconnected, control panel fuse is
removed/installed, etc.), the display automatically
prompts the user for the Time and Date. All other
information is retained in memory.
Programmable Timers
Dealer Programmable
Exercise Time
A programmable exercise time is provided. In the AUTO
mode, the engine starts and runs once each week at the
time and day specified. During the exercise cycle, the
unit runs approximately 12 minutes and then shuts down.
Transfer of loads to the generator does not occur unless
utility power fails.
NOTE:
A Dealer password is required to change the
duration of Exercise Cycle.
User Programmable
Start-Up Delay Timer
A programmable line interrupt delay (or Start-Up Delay)
timer is provided. When utility voltage fails (falls below
60% of nominal), the start-up delay timer is started. If the
voltage rises above the Utility Volts Low threshold, the
timer is reset. If the utility voltage remains below the
threshold during the duration of the timer, the unit cranks
and starts.
NOTE:
The factory default setting is five seconds, but is
adjustable from 2 to 1500 seconds.
Warm-Up Delay Timer
A programmable Warm-Up Delay timer is provided. As
soon as the generator starts, the warm-up timer is
started. When the warm-up timer expires, the control
transfers load to the generator (through the transfer
switch) if the utility voltage is less than 80% of nominal. If
utility voltage is greater than the threshold at expiration of
the warm-up time, the load is not transferred to the
generator and a cool-down period begins. At the end of
the cool-down period, the generator stops.
NOTE:
The factory default setting is five seconds, but is
adjustable from 5 to 1500 seconds.
USB Port for Firmware Updates
A USB port is located beneath the rubber flap on the
control panel and is provided for firmware updates.
Firmware updates must be performed by an Independent
Authorized Service Dealer.
NOTE:
The USB port is intended for use with a USB
thumb drive only. The USB port is not intended for
charging devices such as phones or laptops. Do not
connect any consumer electronics to the USB port.
Contact an IASD for any firmware updates.