Product Manual

Quiet Test Mode?
Yes No
Display Reads:
Use UP ARROW or DOWN ARROW to
select either Yes or No.
Press ENTER.
Select YES to perform exercise at low speed. Select
NO to perform exercise at normal operating speed.
Select Hour (0-23)
- 1 +
Display Reads:
Set Exercise Time.
Use UP ARROW or DOWN ARROW to
increme
nt or decrement the hour. Press
ENTER.
Use UP ARROW or DOWN ARROW to
increme
nt or decrement the minute.
Press ENTER.
Use UP ARROW or DOWN ARROW to
scroll to the day of the w
eek. Press
ENTER.
In the AUTO mode, the engine starts and runs once
each wee
k at the time and day specified. During the
exercise cycle, the unit runs approximately 12 minutes
and then shuts down. Transfer of loads to the generator
does not occur unless utility power fails.
Activation and Startup
16 Owner’s Manual for Stationary Generators
Start and Run Engine
1. See Figure 3-5. Pull up rubber flap covering fuse
holder and verify installation of 7.5 amp fuse (A).
2. Move
the Main Circuit Breaker switch down to the
OFF (Open) position (B).
3. V
erify both auxiliary shutdown switches are ON (I).
See Figure 3-6 for the locations.
4. Pr
ess MANUAL on the control panel (C) to start the
engine. A blue LED illuminates to confirm that the
system is in the MANUAL mode.
5. Allo
w the engine to run until it reaches normal
operating temperature.
6. Pr
ess OFF on the control panel to stop the engine.
A red LED illuminates to confirm that the system is
in the OFF mode.
o
OFF
PUSH TO TRIP
006374
A
B
C
Figure 3-5. Generator Control Panel
Operational Checks
NOTE: The following procedures require special tools
and skills. Contact an IASD to perform these tasks.
Self Test
Upon power up, the controller goes through a system self
test which checks for the presence of utility voltage on
the DC circuits. This is done to prevent damage if the
installer mistakenly connects AC utility power sense
wires into the DC terminal block. If utility voltage is
detected, the controller displays a warning message and
locks out the generator, thereby preventing damage to
the controller. Remove power to the controller to clear
this warning.
Utility voltage must be turned on and present at the N1
an
d N2 terminals inside the generator control panel for
this test to be performed and pass.
Before starting, comp
lete the following:
1. V
erify the generator is OFF. A red LED on the con-
trol panel illuminates to confi
rm that the system is
in the OFF mode.
2. V
erify the Main Circuit Breaker switch on the
generator control panel is in the OFF (Open)
position.
3. T
urn off all circuit breakers/electrical loads that will
be powered by the generator.
4. V
erify both auxiliary shutdown switches are ON (I).
See Figure 3-6 for the locations.
5. Che
ck the coolant and engine lubricating oil levels.
See Check Coolant Level and Hoses and Check
Lubricating Oil Level and Drain Hose.