Install Manual
Installation Guidelines for Protector Diesel Generators 45
Installation Drawings
D3.4L G16 Single Wall (10000042752, page 1 of 2)
892 [35.1]
CENTER OF GRAVITY
SEE NOTE 5
146 [5.7]
EXHAUST OUTLET
173 [6.8]
897 [35.3]
DOOR WIDTH
TYP
1414.4 [55.7]
OVERALL
HEIGHT
888.1 [35.0]
OVERALL WIDTH
301.9 [11.9]
TYP
1322 [52.0]
TYP
1953.8 [76.9]
OVERALL LENGTH
182.4 [7.2]
TYP
WEIGHT DATA WITH EMPTY BASETANK
(SEE NOTE 5)
GENERATOR AS SHOWN
886 [1953]
WITH WOODEN SHIPPING SKID
925 [2039]
SERVICE ITEM 3.4L
OIL FILL CAP RIGHT SIDE
OIL DIP STICK RIGHT SIDE
OIL FILTER RIGHT SIDE
OIL DRAIN HOSE RIGHT SIDE
RADIATOR DRAIN HOSE LEFT SIDE
AIR CLEANER ELEMENT RIGHT SIDE
MUFFLER FRONT
FAN BELT EITHER SIDE
BATTERY LEFT SIDE
NOTES:
 1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194 (47") WIDE X 2718 
 (107") LONG. REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT
 FOR CONCRETE PAD GUIDELINES
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
 AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
 APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
 STATE AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
 - SEE SPECIFICATION SHEET OR OWNERS MANUAL
 - ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF 
 GENERATOR
4. REMOVE THE REAR TANK AND REAR ENCLOSURE COVER PANEL TO ACCESS
 THE STUB-UP AREAS AS FOLLOWS:
 - HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION,
 NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
 - LOW VOLTAGE CONNECTIONS INCLUDING TRANSFER SWITCH CONTROL WIRES
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. ENGINE SERVICE CONNECTIONS
 OIL DRAIN: 3/8" NPT
 EXHAUST OUTLET: 2" O.D.
7. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
 RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
8. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
9. MOUNTING BOLTS OR STUDS TO CONCRETE PAD SHALL BE 5/8-11 GRADE 5
 (USE STANDARD SAE TORQUE SPECS)
REFERENCE OWNERS MANUAL FOR PERIODIC
REPLACEMENT PART LISTINGS.
WEIGHT: KG [LBS]
DIMENSIONS: MM [INCH]
CIRCUIT BREAKER
SEE NOTE 3
REAR VIEW
REAR ENCLOSURE 
COVER PANEL
SEE NOTE 4
CUSTOMER ACCESS 
ASSEMBLY, CONTROL 
PANEL ACCESS AND 
BATTERY CHARGER 
LOCATED WITHIN
SEE NOTE 4
REMOVABLE 
STUB-UP COVER
SEE NOTE 4
RIGHT SIDE VIEW
VISE ACTION LATCH, ONE PER 
DOOR AND ONE LIFT-OFF DOOR 
PER SIDE OF THE GENERATOR
LIFTING PROVISIONS SEE 
NOTE 5, 8 AND CENTER 
OF GRAVITY DIMENSION
(4 PLACES)
LEFT SIDE VIEW
RADIATOR/EXHAUST
DISCHARGE AIR
 GENERATOR ENCLOSURE
 ENCLOSED WITHIN
EXHAUST MUFFLER
 VENTILATION
 CROSS-FLOW OF AIR
 PROVIDE ADEQUATE
 VENTILATION DUCT TO
 OF FUEL TANK
 TYPICAL ON BOTH SIDES
OPEN PUNCHED LOUVERS,
TOP VIEW
BATTERY 12 VOLT
NEGATIVE GROUND
AIR INTAKE
(BOTH SIDES)
REMOVE COVER 
FOR ACCESS TO 
RADIATOR FILL CAP
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)