Install Manual
Installation Checklists
32 Installation Guidelines for Protector Diesel Generators
 Does installation appear to have necessary accesso-
ries  to  allow  fast,  reliable  starting  and  operation  in
adverse  weather  conditions  (such  as  engine  block
heaters, battery warmers, etc.)?
  Do  these  parameters  meet  all  applicable  codes  and
local jurisdiction?
Exhaust System Checklist
NOTE: See Diesel Fuel Systems for more information.
 Are exhaust discharges directed away from combusti-
ble surfaces and inhabited areas?
 Is exhaust piping kept clear of fuel supply, fuel lines,
etc.?
  Is  off-engine  exhaust  piping  covered  with  high  tem-
perature insulation blankets where necessary?
  Do  these  parameters  meet  all  applicable  codes  and
local jurisdiction?
Fuel System Checklist
NOTE: See Diesel Fuel Systems for more information.
  Was  an  approved  pipe  sealant  or  joint  compound
used on all threaded fittings?
  Was  installation  of  an  emergency  safety  shutoff
required? Was correct operation of emergency shutoff
verified?
 Was Final Operating Test performed to verify system
operates correctly in all modes of operation? 
  Is  there  any  evidence  of  leakage  at  any  hoses,
clamps, or fittings?
  Do  these  parameters  meet  all  applicable  codes  and
local jurisdiction?
Electrical System Checklist 
NOTE: See Electrical System for more information.
 Is all wiring correctly sized for load and length of run?
 Is all wiring correctly routed? 
 Is all wiring correctly connected? 
 Are wire lugs fastened to buss bars using appropriate
hardware?  Is  hardware  correctly  tightened  to  speci-
fied torque?
 Are all other terminals correctly tightened using speci-
fied torque?
 Are batteries correctly sized?
 Are batteries correctly installed?
 Are battery fluid levels correct?
 Are battery cables and connections clean and free of
corrosion?
 Are battery cables correctly connected? Are terminal
lugs correctly tightened? 
 Is battery condition and state of charge acceptable?
 Is area housing storage battery correctly ventilated?
 Are batteries located near a source of flame or spark? 
 Are AC wire sizes and connections correct?
  Are  DC  and  communication  wire  sizes  and  connec-
tions correct? 
  Are  block  heaters,  battery  charger,  etc.  correctly
matched with utility supply voltage?
  Are  battery  charger  and  block  heater  correctly  con-
nected?
  Are  remote  start  Wires  178  &  183  pulled  and  con-
nected  inside  lower  control  panel  of  generator  and
inside transfer switch?
 Is AUTO/OFF/MANUAL mode OFF? (Leave in AUTO
when installation is completed.)
 Is block heater operational?
 Is battery charger operational?
  Are  all  AC  electrical  connections  tight  at  circuit
breaker and transfer switch?
 Are two auxiliary shutdown switches ON (I)?
  Are  all  electrical  connections  (wiring,  wire  ties,
clamps,  terminal  ends,  connectors)  on  generator
tight?
  Are  all  electrical  plugs  throughout  generator  seated
correctly and fully inserted into their receptacles?
 Is there correct voltage and phase rotation at transfer
switch?
  Is  manual  operation  of  transfer  switch  smooth  and
non-binding?
  Do  these  parameters  meet  all  applicable  codes  and
local jurisdiction?