Install Manual
Electrical System
22 Installation Guidelines for Protector Diesel Generators
Control Wiring Connections
The control wire customer connection block is where all
of control wiring is connected. 
NOTE: All wiring must comply with NEC, state, and local
AHJ  requirements.  Control  wiring  shall  be  installed  per
the requirements of NEC Articles 300.3(C) and 725.46. If
installing conductors with different voltage insulation rat-
ings, a 600V rated electrical sleeve is provided and can
be found in the manual bag.
See Figure 5-4. Depending on the type of system, con-
trol wiring includes the following. (Wire colors shown for
illustration purposes only):
Figure 5-4. Control Wiring Connections (Typical)
RTS Series Transfer Switch With T1 Fuse/
Connection
NOTE:  The  control  wire  customer  connections  require
the  use  of  Class  1  Wiring  Methods. Always  follow  the
standards  and  methods  appropriate  to  circuits  being
wired.
NOTE: T1 is the 120 VAC power supply for control panel
battery  charger.  This  circuit  must  be  powered  whether
transfer switch is in utility or standby mode. Control board
will generate a warning (Battery Charge AC Fail) if circuit
loses power.
NOTE:  Observe  maximum  wire  size  for  terminal  strip
connections shown in unit wiring diagram.
(1) For battery charging, connect neutral in TB2 to neutral
in transfer switch. See NOTE below for transfer switches
without T1.
(2)  Connect  T1  in  TB2  to  T1  in  transfer  switch.  This  is
120  volt  supply  to  unit's  battery  charger  (normal  RTS
transfer switch). 
(3) (4) Connect N1, N2 sensing wires in TB2 to N1 and
N2 in transfer switch. These two wires are utility sensing
wires. 
(5) (6) Connect 23 in TB3 to 23 in transfer switch. Con-
nect  194  in  TB3  to  194  in  transfer  switch.  These  are
transfer switch control wires.
RTS Series Transfer Switch Without T1 Fuse/
Connection
Use a 120 volt generator protected circuit from the panel
board to power the battery charger circuit (dedicated 15/
20 amp circuit). See installation manual.
Two-Wire Start
To  convert  transfer  switches  to  two-wire  start  mode  of
operation, contact an IASD for panel conversion and con-
nection of terminals 178 and 183 in TB3. Use a 120 volt
generator  protected  circuit  from  panel  board  to  power
battery charger circuit (dedicated 15/20 amp circuit).
The generator  controller will  have  to be  re-programmed
for two-wire start by an IASD.
TB2 Terminal Block
Terminal Function Voltages
1
Neutral Neutral for T1 battery charger Neutral
2
T1 Power for T1 battery charger 120 VAC
3
N2 Utility Sensing from transfer switch 208-277 VAC
4
N1 Utility Sensing from transfer switch 208-277 VAC
TB3 Terminal Block
Terminal Function Voltages
A
178 Two wire start control [GTS] 5-12 VDC
B
183 Two wire start control [GTS] 5-12 VDC
5
23 Transfer relay control wire 12-0 VDC
6
194 Power for transfer relay  12 VDC
1
2
3
4
A
B
5
6










