Install Manual
Electrical System
Installation Guidelines for Protector Diesel Generators 19
Section 5: Electrical System
General Information
All wiring must be correctly sized, routed, supported, and
connected. All  wiring  must  comply  with  NEC  and  local
codes.
The  generator  uses  Customer  Connection  Interface
(CCI) panels to separate high voltage and customer con-
trol  wiring  connections.  These  two  panels  are  clearly
labeled. The wiring diagrams for each specific unit show
the  connection  points  in  their  corresponding  sections.
Terminal  boards  are  clearly  labeled  and  correspond  to
the same  terminal  connections  shown  in  the  wiring  dia-
grams. Always  use  unit  specific  wiring  diagrams  when
making wiring connections.
NOTE: See Alternator AC Lead Connections.
Connecting Generator Feeder 
Conductors
Installation and interconnection diagrams are provided at
the back of this manual.
NOTE: All installations must comply with national, state,
and local codes. It is the responsibility of the installer to
perform  an  installation  that  will  pass  the  final  electrical
inspection.
The generator supply connection is made at the genera-
tor disconnect circuit breaker terminals. Conductor sizes
must  be  adequate  to  handle  the  maximum  current  to
which they will be subjected, based on the 75 °C column
of tables, charts, etc. used to size conductors. The instal-
lation  must  fully  comply  with  all  applicable  codes,  stan-
dards, and regulations.
All  power  cables  can  enter  the  enclosure  through  the
knockouts provided. 
NOTE:  Apply  corrosion  inhibitor  to  conductors  if  alumi-
num conductors are used. 
Tighten terminal lugs to the torque values as noted on the
decal  located  on  the  inside  of  the  door. After  tightening
terminal lugs, carefully wipe away any excess corrosion
inhibitor.
Connect generator conductors to clearly marked terminal
lugs in generator as follows:
1. Connect generator conductors to disconnect circuit
breaker.
2. Connect generator neutral to neutral terminal bar.
3. Connect  equipment  ground  to  equipment  ground
lug.
Connecting Start Circuit Wires
Control system interconnections may consist of N1, N2,
and T1, and leads 23 and 194. The generator control wir-
ing is a Class 1 signaling circuit. See instruction manual
of specific engine generator for wiring connection details.
Recommended wire gauge sizes for this wiring depends
on  the  wire  length,  as  recommended  in  the  following
chart:
Exception:  Conductors  of  AC  and  DC  circuits,  rated
1,000 volts nominal, or less, shall be permitted to occupy
the  same  equipment,  cable,  or  conduit.  All  conductors
shall have an insulation rating equal to at least the maxi-
mum circuit  voltage  applied  to  any  conductor  within  the
equipment, cable, or conduit. See NEC 300.3(C)(1).
Electrocution. Turn utility and emergency
power supplies to OFF before connecting 
power source and load lines. Failure to do so 
will result in death or serious injury. 
(000116)
DANGER
Maximum Wire Length Recommended Wire Size
1–115 ft (0.3–35 m) No. 18 AWG
116–185 ft (36–56 m) No. 16 AWG
186–295 ft (57–89 m) No. 14 AWG
296–460 ft (90–140 m) No. 12 AWG
(000120)
CAUTION
Equipment damage. Verify all conductors are tightened 
to the factory specified torque value. Failure to do so 
could result in damage to the switch base.










