Install Manual
Site Selection and Preparation
Installation Guidelines for Protector Diesel Generators 15
Mounting
Fixed Foundation
Use mounting holes in base frame to fasten unit to foun-
dation. Always  use  hardware  of  a  suitable  grade,  size,
and style. 
Connections
All  electrical  connections  must  have  flexible  sections  to
isolate vibration if they connect to the unit base rails. Cor-
rectly support and secure all piping before installing flexi-
ble connection.
Combustible Floor and Roof Protection
Engines,  and  their  weatherproof  housings,  if  provided,
that are installed on roofs of structures shall be located at
least 5 ft (1.5 m) from openings in walls and at least 5 ft
(1.5  m)  from  structures  having  combustible  walls.  Per
NEC 110.26(E)(2), a minimum separation of 3 ft (0.91 m)
is permitted if the adjacent wall of the structure has a fire
resistance rating of at least 1 hour.
An  oil  containment  system  consisting  of  a  curb  or  dike
having  a  capacity  at  least  equal  to  the  total  capacity  of
the lubricating oil system or the liquid fuel system, which-
ever is greater, shall be provided. This system shall also
comply with applicable requirements of NFPA 37, Chap-
ter 6.
The surface beneath the engine and beyond the engine
and the oil containment dike shall be noncombustible to a
minimum distance of 12 in (300 mm).
NOTE:  Local  building  codes  may  have  additional  re-
quirements for placement of fuel storage tanks on top of
a  roof  or  structure.  Contact  the  local  building  code
department  or  fire  marshal  for  code  compliance  before
placing generator on top of roof or structure.