Liquid Cooled Gas Engine Generator Sets Specification Sheet

COMMERCIAL 70 kW
KW RATING 70
ENGINE SIZE 6.8 Liter V-10
GENERATOR OUTPUT VOLTAGE/KW - 60 Hz KW AMP CB Size
120/240V, single phase, 1.0 pf 70 LP / 68 NG 291.6 LP / 283.3 NG 300
120/208V, 3-phase, 0.8 pf 70 LP / 68 NG 243.1 LP / 236.2 NG 300
120/240V, 3-phase, 0.8 pf 70 LP / 68 NG 210.7 LP / 204.7 NG 250
277/480V, 3-phase, 0.8 pf 70 LP / 68 NG 105.3 LP / 102.4 NG 125
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208V & 240V 3-phase 145
480V 3-phase 160
ENGINE FUEL CONSUMPTION
(Natural Gas) (Propane) Natural Gas Propane
(ft
3
/hr.) (gal/hr.) cu ft/hr
Exercise cycle 110 1.20 44.2
25% of rated load 260 2.85 104.9
50% of rated load 499 5.46 200.9
75% of rated load 696 7.62 280.4
100% of rated load 1020 11.17 411
ENGINE COOLING
Air flow
(inlet air including alternator and combustion air) ft
3
/min. 5200
System coolant capacity US gal. 4.5
Heat rejection to coolant BTU/hr. 287,000
Max. operating air temp. on radiator °C (°F) 60 (150)
Max. ambient temperature °C (°F) 50 (140)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz cfm 205
SOUND EMISSIONS IN DBA
db(A) @ 23 feet in exercise mode 61
db(A) @ 23 feet at normal operating load 65
EXHAUST
Exhaust flow at rated output 60 Hz cfm 557
Exhaust temp. at muffler outlet °F 890
ENGINE PARAMETERS
Rated synchronous RPM 60 Hz 1800
HP at rated KW 60 Hz 110.7
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration
3% for every 10 °C above - °C 25
1.65% for every 10 °F above - °F 77
Altitude Deration
1% for every 100 m above - m 183
3% for every 1000 ft. above - ft. 600
OPERATING DATA
COMMERCIAL 70 kW
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility
source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and
specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power
and condition, etc.
COMMERCIAL SERIES