Spec Sheet
Amps 600 800
Voltage 120/240, 1ø
120/208, 3ø
120/240, 3ø
277/480, 3ø
120/240, 1ø
120/208, 3ø
120/240, 3ø
277/480, 3ø
Load Transition Type
(Automatic)
Open Transition Open Transition
Enclosure Type NEMA 3R NEMA 3R
Withstand Rating (Amps) 42,000 65,000
Lug Range 1/0 - 500 MCM 4/0 - 500 MCM
External Dimensions
Height Width
Depth
Height Width
Depth
H1 H2 W1 W2 H1 H2 W1 W2
61.4 66 30 36 21 61.4 66 30 36 21
120/240, 1ø
61.4 66 30 36 21 61.4 66 30 36 21120/208, 3ø
120/240, 3ø 61.4 66 30 36 21 61.4 66 30 36 21
277/480, 3ø
61.4 66 30 36 21 61.4 66 30 36 21
Unit Weight (lbs.) 439 469
RTS 600-800 Amp Transfer Switch
®
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2010 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0190980SBY-A / Printed in U.S.A. 12/13/10
FUNCTIONS
All Timing and sensing functions originate in the generator controller
Utility voltage drop-out ......................................................................................................................................................................................................................<60%
Timer to generator start ...................................................................................................................................... 10 second factory set, adjustable between 10-30 seconds
Engine warm up delay .................................................................................................................................................................................................................5 seconds
Standby voltage sensor ..................................................................................................................................................................................................60% for 5 seconds
Utility voltage pickup .........................................................................................................................................................................................................................>80%
Re-transfer time delay ...............................................................................................................................................................................................................15 seconds
Engine cool-down timer ............................................................................................................................................................................................................ 60 seconds
Exerciser .............................................................................................................................................................................................................. 12 minutes every 7 days
The transfer switch can be operated manually without power applied.
SPECIFICATIONS
TRANSFER SWITCH FEATURES
• Electrically operated, mechanically-held contacts for fast, positive connections.
• Rated for all classes of load, 100% equipment rated, both inductive and resistive.
• 160 millisecond transfer time.
• Dual coil design.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
• NEMA 3R (indoor/outdoor rated) aluminum enclosure is standard.
• Limited Two Year Warranty.