Product Manual
Table Of Contents
- Owner’s Manual 60 Hz Air-Cooled Generators
- Table of Contents
- Section 1: Safety Information
- Section 2: General Information
- Section 3: Operation
- Site Prep Verification
- Generator Enclosure
- Auxiliary Shutdown Switch
- Control Panel Interface
- Using the AUTO/OFF/MANUAL Buttons
- Operating Modes
- Interface Menu Displays
- Menu System Navigation
- Setting the Exercise Timer
- Battery Charger
- Manual Transfer Operation
- Automatic Transfer Operation
- Automatic Sequence of Operation
- Shutting Generator Down While Under Load or During a Utility Outage
- Section 4: Maintenance
- Maintenance
- Preparing for Maintenance
- Performing Scheduled Maintenance
- Service Schedule
- Checking Engine Oil Level
- Changing the Oil and Oil Filter
- Servicing the Air Cleaner
- Spark Plug(s)
- Valve Clearance Adjustment
- Battery Maintenance
- Cleaning the Sediment Trap
- Post Maintenance Checks
- Attention After Submersion
- Corrosion Protection
- Remove From and Return To Service Procedure
- Section 5: Troubleshooting / Quick Reference Guide
Troubleshooting / Quick Reference Guide
38 Owner’s Manual for 60 Hz Air-Cooled Generators
AUXILIARY
SHUTDOWN
RED Unit will not start.
Check auxiliary
shutdown switches
Set auxiliary shutdown switch(es) to
CLOSED (I). Clear alarm.
LOW BATTERY YELLOW
Yellow LED illuminated
in any state.
Check screen for
additional information.
Clear alarm. Using control panel, check
battery by navigating to BATTERY MENU
option from MAIN MENU. If battery condi-
tion displays GOOD, contact an IASD. If
control panel displays CHECK BATTERY,
replace battery.
BATTERY
PROBLEM
YELLOW
Yellow LED illuminated
in any state.
Check screen for
additional information.
Contact an IASD.
CHARGER
WARNING
YELLOW
Yellow LED illuminated
in any state.
Check screen for
additional information.
Contact an IASD.
CHARGER
MISSING AC
YELLOW
Yellow LED illuminated
in any state.
Check screen for
additional information.
Contact an IASD.
SERVICE A YELLOW
Yellow LED illuminated
in any state.
Check screen for
additional information.
Perform SERVICE A maintenance. Press
ENTER to clear.
SERVICE B YELLOW
Yellow LED illuminated
in any state.
Check screen for
additional information.
Perform SERVICE B maintenance. Press
ENTER to clear.
INSPECT
BATTERY
YELLOW
Yellow LED illuminated
in any state.
Check screen for
additional information.
Inspect battery. Press ENTER to clear.
Active Alarm LED Problem Action Solution