Control Panel Startup / Testing
Installation Guidelines for 60 Hz Air-Cooled Generators 39
Checking Manual Transfer Switch 
Operation
See Manual Transfer Operation section of owner’s man-
ual for procedures.
Electrical Checks
Proceed as follows to complete electrical checks:
1. Verify generator is in OFF mode.
2. Set  generator  MLCB  (generator  disconnect)  to
OFF (OPEN).
3. Turn  off  all  circuit  breakers/electrical  loads  to  be
supplied by generator.
4. Turn on utility power supply to transfer switch using
means provided (such as a utility MLCB). 
5. Use a calibrated AC voltmeter to verify utility power
source voltage across transfer switch terminals N1
and N2. Nominal line-to-line voltage should be 240
volts AC.  If  voltage  is  incorrect,  verify AC  output
and wiring from utility source to N1 and N2 lugs at
transfer switch.
6. Verify utility power source voltage across terminals
N1 and transfer switch neutral lug; then across ter-
minal N2 and neutral. Nominal line-to-neutral volt-
age  should  be  120  volts  AC  (if  wired  with  a
neutral). If voltage is incorrect, verify AC output and
wiring  from  utility  source  to  N1  and  N2  lugs  at
transfer switch.
7. Turn off utility power supply to transfer switch when
utility  supply  voltage  is  verified  to  meet  specifica-
tion provided in Step 6.
8. Press  MANUAL mode button  on  generator panel.
The  engine  will  crank  and  start.  Record  cranking
fuel pressure: ______________.
9. Allow  engine  to  warm  up  for  approximately  five
minutes for internal temperatures to stabilize. Then
set generator MLCB (generator disconnect) to ON
(CLOSED).  Record  running  fuel  pressure:
______________.
10. Connect a calibrated accurate AC voltmeter and a
frequency  meter  across  transfer  switch  terminal
lugs E1 and E2. Voltage should be 238–242V at a
frequency of 59.5–60.5 Hz. If voltage is incorrect,
verify  generator  MLCB  (generator  disconnect)  is
closed, and verify AC output and frequency (Hertz
or Hz) at generator MLCB (generator disconnect).
Verify  wiring from generator to  E1 and E2  lugs at
transfer switch.
11. Connect AC  voltmeter  test  leads  across  terminal
lugs E1 and neutral, then across E2 and neutral (if
wired with a neutral). In both cases, voltage read-
ing should be 119–121 volts AC. If voltage is incor-
rect, verify generator MLCB (generator disconnect)
is closed, and verify AC output between E1 and E2
of  generator  MLCB  (generator  disconnect)  and
neutral at generator. 
12. Verify wiring from generator to E1, E2, and neutral
lugs at transfer switch.
13. Set  generator  MLCB  (generator  disconnect)  to
OFF (OPEN).
14. Press generator OFF mode button. The engine will
shut down.
IMPORTANT NOTE: DO NOT proceed until generator
AC  voltage  and  frequency  are  correct  and  within
stated limits.
Generator Tests Under Load
Proceed as follows to test generator with electrical loads
applied:
1. Verify generator is in OFF mode. 
2. Set  generator  MLCB  (generator  disconnect)  to
OFF (OPEN).
3. Turn  off  all  circuit  breakers/electrical  loads  to  be
supplied by generator.
4. Turn off utility power supply to transfer switch using
means provided (such as a utility MLCB).
5. Manually  set  transfer  switch  to  STANDBY,  with
load terminals connected to generator’s E1/E2 ter-
minals.  Transfer  switch  operating  lever  should  be
down.
6. Press generator MANUAL button. Engine will crank
and start immediately.
7. Verify fuel pressure while cranking. Record crank-
ing fuel pressure:________
8. Allow  engine  to  stabilize  and  warm  up  for  a  few
minutes.
(000129)
DANGER
Electrocution. High voltage is present at 
transfer switch and terminals. Contact with live 
terminals will result in death or serious injury.
(000129)
DANGER
Electrocution. High voltage is present at 
transfer switch and terminals. Contact with live 
terminals will result in death or serious injury.
(000132)
Electrocution. Do not manually transfer under load. 
Disconnect transfer switch from all power sources 
prior to manual transfer. Failure to do so will result in 
death or serious injury, and equipment damage.
DANGER