Install Manual
Table Of Contents
- Installation Guidelines 60 Hz Air-Cooled Generators
- Table of Contents
 - Section 1: Safety Rules & General Information
 - Section 2: Unpacking and Inspection
 - Section 3: Site Selection and Preparation
 - Section 4: Generator Placement
 - Section 5: Fuel Conversion / Gas Connections
 - Section 6: Electrical Connections
 - Section 7: Control Panel Startup / Testing
 - Section 8: Troubleshooting
 - Section 9: Quick Reference Guide
 - Section 10: Accessories
 - Section 11: Diagrams
 
 
Site Selection and Preparation
16 Installation Guidelines for 60 Hz Air-Cooled Generators
Fire Codes, Standards, and Guidelines
Generator  installation  must  comply  strictly  with  ICC
IFGC, NFPA 37, NFPA 54, NFPA 58, and NFPA 70 stan-
dards.  These  standards  prescribe  the  minimum  safe
clearances around and above the generator enclosure.
NFPA 37
NFPA  37  is  the  The  National  Fire  Protection  Associa-
tion’s  standard  for the  installation  and  use  of  stationary
combustion engines. Its requirements limit the spacing of
an enclosed generator set  from a  structure or wall, and
require generator to be located where it is readily acces-
sible for maintenance, repair, and first responders.
NFPA  37,  Section  4.1.4,  Engines  Located  Outdoors:
Engines,  and  their  weatherproof  housings  if  provided,
installed outdoors shall be located at least 5 ft (1.52 m)
from  openings  in  walls  and  at  least  5  ft  (1.52  m)  from
structures having combustible walls. A minimum separa-
tion  shall  not  be  required  where  either  of  the  following
conditions exist:
1. The adjacent wall of the structure has a fire resis-
tance rating of at least one hour.
2. The weatherproof enclosure is constructed of non-
combustible  materials  and  it  has  been  demon-
strated that a fire within the enclosure will not ignite
combustible materials outside the enclosure.
Annex A—Explanatory Material
A4.1.4  (2)  Means  of  demonstrating  compliance  are  by
means of full scale fire test or by calculation procedures.
Because  of  the  limited  spaces  frequently  available  for
installation,  it  has  become  apparent  that  exception  (2)
would be beneficial for many residential and commercial
installations. The manufacturer  contracted with  an  inde-
pendent testing laboratory to run full scale fire tests.
NOTE:  The  Southwest  Research  Institute  (SwRI)  is  a
nationally  recognized  third  party  testing  and  listing
agency. SwRI testing approves 18 in (457 mm) installa-
tion minimum from the rear panel of the generator to an
adjacent structure for fire protection. 
The criteria was to determine the worst case fire scenario
within  the  generator  and  to  determine  the  ignitability  of
items outside the engine enclosure at various distances.
The enclosure is constructed of non-combustible materi-
als,  and  the  results  and  conclusions  from  the  indepen-
dent  testing  lab  indicated  that  any  fire  within  the
generator  enclosure would  not  pose  any  ignition  risk  to
nearby  combustibles  or  structures,  with  or  without  fire
service personnel response.
Figure 3-3. Southwest Research Institute Marking
http://www2.swri.org/www2/listprod/
DocumentSelection.asp?ProductID=973&IndustryID=2
Based on this testing and the requirements of NFPA 37,
Sec 4.1.4, the guidelines for installation of the generators
listed  above  are  changed  to  18  in  (457  mm)  from  the
back side of the generator to a stationary wall or building
For  adequate  maintenance  and  airflow  clearance,  the
area above the generator should be at least 5 ft (1.52 m)
with a minimum of 3 ft (0.91 m) at the front and ends of
the enclosure. This includes trees,  shrubs, and  bushes.
Vegetation  not  in  compliance  with  these  clearance
parameters  could  obstruct  air  flow.  In  addition,  exhaust
fumes from the generator could inhibit plant growth. See
Figure 3-2 and the accompanying descriptions.
Generator Maintenance 
Regular  maintenance  is  crucial  for  minimizing  exhaust
emissions and reducing the risk of fire or equipment fail-
ure. For example:
• A  dirty  air  filter  or  low  engine  oil  level  may  cause
engine to overheat. 
• Incorrect spark plug gaps may cause engine back-
firing and incomplete combustion.
IMPORTANT  NOTE:  See  Maintenance  section  of
generator owner’s  manual to  view  a table  of  sched-
uled maintenance tasks and procedures. Perform all
maintenance tasks as directed.
002158










