Install Manual
Table Of Contents
- Installation Guidelines 60 Hz Air-Cooled Generators
- Table of Contents
 - Section 1: Safety Rules & General Information
 - Section 2: Unpacking and Inspection
 - Section 3: Site Selection and Preparation
 - Section 4: Generator Placement
 - Section 5: Fuel Conversion / Gas Connections
 - Section 6: Electrical Connections
 - Section 7: Control Panel Startup / Testing
 - Section 8: Troubleshooting
 - Section 9: Quick Reference Guide
 - Section 10: Accessories
 - Section 11: Diagrams
 
 
Unpacking and Inspection
Installation Guidelines for 60 Hz Air-Cooled Generators 11
Auxiliary Shutdown Switch
All  generators  are  equipped  with  an  external  means  of
shutting down the generator which complies with the lat-
est NEC code requirement. The primary generator shut-
down sequence is described in Control Panel Startup /
Testing. 
See  Figure  2-11.  An  auxiliary  shutdown  switch  (A)  is
located on the exterior of the generator back panel. This
switch shuts down the generator and disables restarts.
Figure 2-11. Auxiliary Shutdown Switch (all models)
NOTE:  Whenever  possible,  perform  primary  shutdown
procedure before disabling generator with auxiliary shut-
down switch.
See Figure 2-12. 14–24 kW generators have an auxiliary
shutdown switch (B) located inside the generator. 
Figure 2-12. Auxiliary Shutdown Switch (14–24 kW)
NOTE:  Generator will not start if either switch is  OPEN
(O).  Controller  displays  an  “Auxiliary  Shutdown”  alarm,
and  red  LED  “Alarm”  light  illuminates  until  switch  or
switches are CLOSED (I) and alarm is cleared by press-
ing OFF mode button, and then ENTER. Once cleared,
generator can be placed back in AUTO or MANUAL.
Equipment Damage. The auxiliary shutdown switch 
is not to be used to power down the unit under 
normal operating circumstances. Doing so will 
result in equipment damage.
(000399)
CAUTION
005491
A
005492
B










